CS-UE9JKE, CS-UE12JKE, CU-UE9JKE, CU-UE12JKE - Panasonic Air Conditioner Service Manual (repair manual). Page 36

Read Panasonic CS-UE9JKE / CS-UE12JKE / CU-UE9JKE / CU-UE12JKE Service Manual online

36 
 
13.1.2  Relationship between the condition of the air conditioner and pressure and electric 
current 
 
Cooling Mode 
Heating Mode 
Condition of the  
air conditioner 
Low Pressure 
High 
Pressure 
Electric current 
during 
operation 
Low Pressure 
High 
Pressure 
Electric current 
during operation
Insufficient 
refrigerant 
(gas leakage) 
Ô 
Ô 
Ô 
Ô 
Ô 
Ô 
Clogged capillary 
tube or 
strainer 
Ô 
Ô 
Ô 
Ò 
Ò 
Ò 
Short circuit in the 
indoor unit 
Ô 
Ô 
Ô 
Ò 
Ò 
Ò 
Heat radiation 
deficiency 
of the outdoor unit 
Ò 
Ò 
Ò 
Ô 
Ô 
Ô 
Inefficient 
compression 
Ò 
Ô 
Ô 
Ò 
Ô 
Ô 
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is 
started. 
 
13.2  Breakdown Self Diagnosis Function 
13.2.1  About Self Diagnosis 
When the air-conditioner is stopped due to malfunction detected by itself, the operation can be restarted using AUTO 
Switch on the indoor unit. In forced operation, the frequency for compressor and fan speed can not be changed and 
the signal receiving sound is different. 
Normal Operation ON: “pep” 
Forced Operation ON: “pep”, “pep”, “pep”, “pep” 
Stop: “pep” 
Note: Refer to the Diagnosis Code Table for the malfunction when forced operation is not available.
 
13.2.2  Display of Error Code 
1. Keeping the CHECK button on the remote controller depressed for 5 seconds, error code ranging from H11 to H99 
can be displayed on the remote controller. 
2. The error code is changed and diagnosis signal is transmitted to the indoor unit by pressing the Temp Up button 
on the remote control. 
3. When the malfunction of the air-conditioner matches the error code on the remote control, four beeps can be heard 
from the indoor unit and the operation indicator will light up. 
4. Keep the CHECK button depressed continuously for 5 seconds to cancel the diagnosis function. 
 
 
 