8.3.
Heating Mode Operation(Only for PA12DKD)
When selecting the Heating Mode Operation, the unit will operate according to the setting by the Remote Controller and
the operation is as the following.
Time Delay Safety Control
Over Load protection Control
When temperature of indoor heat exchanger rises to 51
, outdoor fan will stop
when temperature of indoor heat exchanger falls to 49
, outdoor fan will restart.
When temperature of indoor heat exchanger rises to 65
or above, compressor stops, and will restart 4 minutes later.
4-way valve control
Anti-reversing Control
If the compressor stopped by switching off, turning off by remote controller, or power off, it will not restart within 3 minutes.
When room temperature reaches the set temperature on the remote controller, compressor stops and will not restart within
4 minutes.
3 minutes after the compressor stopped, indoor fan will stop for 1 minute. Then indoor fan will resume operation with the
speed at ”super low”
.
Compressor
Stops
Compressor Restarts
4 minutes later
Indoor Heat Exchanger
65
Compressor
Stops
Compressor Restarts
3 minutes later
Compressor runs
5 min
T
5
last for 2 min
T= intake air temperature - evaporator temperature
If the compressor has been continuously running for 5 minutes or longer, and the difference of temperature between
intake air and evaporator is continuously lower than 5.0
or below for 2 minutes, the compressor will stop , and then
restart 3 minutes later.(Time Delay Protection Control is effective.)
During heating mode operation,4-way valve is at
open
mode.
During heating mode operation,if the unit turned off, the 4-way valve will remain
at
open
mode for 5 minutes.
Low
Super Low
Super Low
Indoor Fan
Stop
Indoor Fan
Stop
Indoor Heat
Exchanger
Indoor Heat
Exchanger
34
30
(
)
(
)
Warm Booting Control
When turning on the unit by heating mode operation,indoor fan
will be activated when temperature of indoor heat exchanger
reaches 30
. (See the figure on the right)
Warm boot operation ends when temperature of indoor heat
exchanger reaches 34
.
20
CS-PC12DKD / CU-PC12DKD / CS-PA12DKD / CU-PA12DKD