CS-MC90KH, CU-MC140KH, CS-MC90KH, CU-MC180KH, CS-MC90KH, CU-3MC200KH - Panasonic Air Conditioner Service Manual (repair manual). Page 35

Read Panasonic CS-MC90KH / CU-MC140KH / CS-MC90KH / CU-MC180KH / CS-MC90KH / CU-3MC200KH Service Manual online

– 34 –
ORDER NO. MAC9807010C3
CS-MC90KH
3 Evacuation
(No refrigerant in the refrigeration cycle)
Procedure:
(1) Connect the vacuum pump to the charge set’s
center hose.
(2) Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward
–76 cmHg [vacuum of 4 mmHg or less].
(3) Close the valve (Lo side) on the charge set, turn
off the vacuum pump, and confirm that the gauge
needle does not move (approximately
5 minutes after turning off the vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted,
replenish as needed.
3-way valve
3-way valve
OPEN
Vacuum pump
Lo
Hi
OPEN
(Indoor unit)
(Outdoor unit)
(Gas side)
(Liquid side)
Open
Open
Untitled-19
6/26/00, 3:41 PM
34
Page of 83