Read Panasonic CS-MC90KH / CU-MC140KH / CS-MC90KH / CU-MC180KH / CS-MC90KH / CU-3MC200KH Service Manual online
– 23 –
ORDER NO. MAC9807010C3
CS-MC90KH
Operation Details
Soft Dry Operation Time Diagram
a b c d e f g h i j k l m n o p q r s t u v
Basic Time
Compressor
Indoor Fan
Outdoor Fan
Operation LED
10’
1’
1’
1’
6’
6’
6’
6’
4’
1’
Cooling ON
Cooling OFF
Soft Dry ON
Soft Dry ON
Soft Dry OFF
1.5°C
1.0°C
SLo
SLo
SLo
Lo
SLo
SLo
SLo SLo
SLo
SLo
SLo
SLo
Indoor
Heat Exchanger
Temp.
Heat Exchanger
Temp.
10°C
2°C
6’
Intake Air
Temperature
Temperature
Set Temp.
<Description of operation>
a – c, p~r :
Cooling Operation
c – p
:
Soft Dry Operation
e – f
:
Soft Dry OFF
j – l
:
60 sec. Forced Operation
q – t
:
Anti Freezing Control
<Condition>
a – h :
When outdoor temperature is high
h – p :
When outdoor temperature is moderate
p – u :
When outdoor temperature is low
Soft Dry operation
Operation
Stop
- - - - -