CS-F24DTE5, CU-L24DBE5, CS-F28DTE5, CU-L28DBE5, CS-F34DTE5, CU-L34DBE5, CS-F43DTE5, CU-L43DBE5, CS-F50DTE5, CU-L50DBE8 - Panasonic Air Conditioner Service Manual (repair manual). Page 117

Read Panasonic CS-F24DTE5 / CU-L24DBE5 / CS-F28DTE5 / CU-L28DBE5 / CS-F34DTE5 / CU-L34DBE5 / CS-F43DTE5 / CU-L43DBE5 / CS-F50DTE5 / CU-L50DBE8 Service Manual online

13.5. Capacity and power consumption
13.5.1. Cooling performance
Model name
Max cooling capacity
Max capacity (kw)
Max power consumption (kw)
CS-F24DTE5 / CU-L24DBE5
6.5
2.3
CS-F28DTE5 / CU-L28DBE5
7.1
2.4
CS-F34DTE5 / CU-L34DBE5
12
3.4
CS-F43DTE5 / CU-L43DBE5
13.5
4.3
CS-F50DTE5 / CU-L50DBE8
16
5.1
Calculation of actual cooling capacity and power consumption:
Example: CS-F24DTE5 / CU-L24DBE5
 • Calculation of the actual cooling capacity and power consumption for the following cooling conditions;
Indoor temperature of 27/19°C and outdoor temperature of 40°C (Standard condition).
Calculation method
 1. 
Find the cooling capacity ratio and the power consumption ratio from the cooling capacity graph and power consumption graph for model CS-
F24DTE5 / CU-L24DBE5.
 • The cooling capacity ratio indicate at the intersection between an outdoor unit air inlet temperature of 40°C on the horizontal axis and an
indoor unit air inlet temperature on 27/19°C is 0.95.
 • The cooling power consumption ratio from the same intersection on the power consumption graph is 1.03.
 2. 
Thus,
 • Actual cooling capacity = cooling capacity ratio x rated cooling capacity = 0.95 x 6.5 = 6.18 (kw).
 • Actual cooling power consumption = cooling power consumption x rated power consumption = 1.03 x 2.45 = 2.52 (kw).
117
Page of 127
Display