 1 
Service Information 
3
 1.1. 
Example of trouble at test operation 
3
 1.2. 
Caution of test operation 
3
 1.3. 
Caution during automatic address setting 
3
 1.4. 
Operation range 
4
 2 
Features 
5
CS-F24DTE5 CU-L24DBE5
CS-F28DTE5 CU-L28DBE5
CS-F34DTE5 CU-L34DBE5
CS-F43DTE5 CU-L43DBE5
CS-F50DTE5 CU-L50DBE8
 2.1. 
Ceiling type 
5
 2.2. 
Outdoor unit 
5
 2.3. 
A brand-new control method 
6
 2.4. 
Wired Remote Control 
7
 2.5. 
Wireless Remote Control 
7
 2.6. 
Group Control Equipment 
8
Air Conditioner
CONTENTS
 Page 
Page
Order No. MAC0504060C2
 3 
Specification 
9
 3.1. 
Product Specification 
9
 4 
Dimensions 
14
 4.1. 
CS-F24DTE5 CS-F28DTE5 
14
 4.2. 
CS-F34DTE5 CS-F43DTE5 CS-F50DTE5 
15
 4.3. 
CU-L24DBE5 CU-L28DBE5 
16
 4.4. 
CU-L34DBE5 CU-L43DBE5 CS-L50DBE8 
17
 5 
Refrigeration Cycle 
18
 6 
Block Diagram 
19
 6.1. 
CS-F24DTE5 CS-F28DTE5 CS-F34DTE5 CS-F43DTE5
CS-F50DTE5 
19
 6.2. 
CU-L24DBE5 CU-L28DBE5 
20
 6.3. 
CU-L34DBE5 CU-L43DBE5 
21
 6.4. 
CU-L50DBE8 
22
 7 
Wiring Diagram 
23
 7.1. 
CS-F24DTE5 CS-F28DTE5 CS-F34DTE5 CS-F43DTE5
CS-F50DTE5 
23
 7.2. 
CU-L24DBE5 CU-L28DBE5 
24
 7.3. 
CU-L34DBE5 CU-L43DBE5 
25
 7.4. 
CU-L50DBE8 
26
 8 
Remote Control Operating Instructions 
27
 8.1. 
Wired remote control 
27
 8.2. 
Wireless remote control 
28
 9 
Operation Control 
29
 9.1. 
Operation mode 
29
 9.2. 
Compressor start control 
29
 9.3. 
Cooling operation 
29
 9.4. 
Heating mode operation 
31
 9.5. 
Louver control 
34
 9.6. 
Odour removing operation 
35
 9.7. 
Energy save operation 
36
 9.8. 
Outdoor fan remaining heat removal control 
36
 9.9. 
Crank case heater control 
36
 9.10. Valve error 
36
 9.11. Pump down operation 
37
 10 Installation Instruction 
38
 10.1. Pipe length 
38
 10.2. Refrigerant additional charge 
40
 10.3. Position of the centre gravity 
40
 10.4. Indoor unit installation 
41
 10.5. Outdoor unit installation  
50
 10.6. Wired remote control installation 
61
 10.7. Wireless remote control installation manual 
68
 10.8. Twin systems installation 
75
 10.9. Twin 
76
 11 Installation and Servicing Air Conditioner Using R410A 
77
 11.1. Outline 
77
 11.2. Tools for installing/servicing refrigerant piping 
78
 11.3. Refrigerant piping work 
82
 11.4. Installation, transferring, servicing 
84
 12 Trouble Shooting Guide 
88
 12.1. For standard installation 
88
 12.2. During twin operation 
90
 12.3. During group control operation 
92
 12.4. Address setting for twin system 
93
 12.5. Address setting for group control system 
94
 12.6. Wiring mistake prevention 
96
 12.7. Test operation and self diagnosis 
97
 12.8. Emergency operation 
101
 12.9. Self-diagnosis 
102
 13 Technical Data 
104
 13.1. Sound data 
104
 13.2. Sound measurement point 
109
 13.3. Reaching distance 
110
 13.4. Discharge and suction pressure 
112
 13.5. Capacity and power consumption 
117
 13.6. Fan performance 
144
 13.7. Safety device 
147
 13.8. Operating characteristics 
148
 14 Replacement Parts 
149
 14.1. Indoor unit 
149
 14.2. Outdoor unit 
158
 15 Electronic Circuit Diagram 
170
 15.1. Indoor unit 
170
 15.2. Outdoor unit 
174
 15.3. Wired remote control 
186
 15.4. Wireless remote control 
187
 15.5. Print pattern 
188
2
1 Service Information
Notice of Address setting for NEW Ceiling / NEW Outdoor Unit.
The new Ceiling / New Outdoor models are possible to have address setting for twin control by automatic when main
power supply is switched on.
(Manual address setting is also possible by using Dip switch on Indoor unit P.C. board.) However, this address setting is only
possible when made proper wiring connection and also Indoor unit should be original virgin unit
.
1.1. Example of trouble at test operation
If found out as following phenomenon at test operation on site, it may have possibility of wrong address setting.
Therefore, please ensure of the address setting.
 1. LCD display of wired remote control had not illuminate although the main power supply switch is ‘on’.
 2. LCD display had indicated as normal illumination when power supply switch is ‘on’, however outdoor unit cannot be operated.
(But, it is necessary to take 3 to 5 minutes for outdoor unit to start from the timing of remote control ON/OFF switch is ‘on’.)
 3. P.C. board had memorized wrong setting information.
 a. If main power supply is switched ‘on’ with the wrong connection.
 b. When changing the connection or combination of units due to re-installation etc.
 • When changing the system from twin control to normal one to one system.
 • When making the replacement of units as master and slave etc.
1.2. Caution of test operation
Do not touch the remote control switch and do not change any wirings for one minute when the main power supply switch is ‘on’.
(Because the unit is having automatic address setting during the first one minute.)
1.3. Caution during automatic address setting
When main power supply switch is ‘on’, the P.C. board will automatically memorized the connecting system.
Consequently, when initial power supply is ‘on’, there will not be interchangeability of units even of the same type and same
capacity unit. Therefore unable to connect the unit to another system.
3
1.4. Operation range
1.4.1. Power Supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be
balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of
the rated voltage.
MODEL
Unit Main Power
Applicable Voltage
CU-
Phase, Volts
Hz
Max
Min
L24DBE5
L28DBE5
L34DBE5
L43DBE5
1~240
50
264
216
1~220
50
242
198
1~230
50
253
207
L50DBE8
3N~380
50
418
342
3N~400
50
440
360
3N~415
50
457
374
1.4.2. Indoor and Outdoor Temperature
 • Model 50Hz CU-L24DBE5, CU-L28DBE5, CU-L34DBE5, CU-L43DBE5, CU-L50DBE8
Operating
Hz
Indoor Temp. (D.B./W.B.) (°C)
Outdoor Temp. (D.B./W.B.) (°C)
Max
Min
Max
Min
Cooling
50
32/23
21/15
43/-
-15/-
Heating
50
27/-
16/-
24/18
-20/-
4
Page of 127
Display

Download Panasonic CS-F24DTE5 / CU-L24DBE5 / CS-F28DTE5 / CU-L28DBE5 / CS-F34DTE5 / CU-L34DBE5 / CS-F43DTE5 / CU-L43DBE5 / CS-F50DTE5 / CU-L50DBE8 Service Manual (Repair Manual)

Here you can read online and download Panasonic CS-F24DTE5 / CU-L24DBE5 / CS-F28DTE5 / CU-L28DBE5 / CS-F34DTE5 / CU-L34DBE5 / CS-F43DTE5 / CU-L43DBE5 / CS-F50DTE5 / CU-L50DBE8 Service Manual in PDF. CS-F24DTE5 / CU-L24DBE5 / CS-F28DTE5 / CU-L28DBE5 / CS-F34DTE5 / CU-L34DBE5 / CS-F43DTE5 / CU-L43DBE5 / CS-F50DTE5 / CU-L50DBE8 service manual will guide through the process and help you recover, restore, fix, disassemble and repair Panasonic CS-F24DTE5 / CU-L24DBE5 / CS-F28DTE5 / CU-L28DBE5 / CS-F34DTE5 / CU-L34DBE5 / CS-F43DTE5 / CU-L43DBE5 / CS-F50DTE5 / CU-L50DBE8 Air Conditioner. Information contained in service manuals typically includes schematics / circuit diagrams, wiring diagrams, block diagrams, printed wiring boards, exploded views, parts list, disassembly / assembly, pcb.