17.4.26  F97 (Compressor Overheating) 
Malfunction Decision Conditions 
š  During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the 
compressor tank temperature sensor. 
 
Malfunction Caused 
š  Faulty compressor tank temperature sensor 
š  2/3 way valve closed 
š Refrigerant 
shortage 
(refrigerant leakage) 
š  Faulty outdoor unit PCB 
š Faulty 
compressor 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 