CS-E18GKDW, CU-E18GKD, CS-E21GKDS, CU-E21GKD - Panasonic Air Conditioner Service Manual (repair manual). Page 7

Read Panasonic CS-E18GKDW / CU-E18GKD / CS-E21GKDS / CU-E21GKD Service Manual online

7
1. Cooling capacities are based on indoor temperature of 27
°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air
temperature of 35
°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20
°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°F
D.B.), 6
°C W.B. (42.8°F W.B.)
Note
• Specifications are subject to change without notice for further improvement.
Heat Exchanger
Fin Material
Aluminium (Pre Coat)
Aluminium (Blue Coated)
Fin Type
Slit Fin
Corrugated Fin
Row x Stage x FPI
2 x 15 x 19
2 x 34 x 18
Size (W x H x L)
mm
810 x 315 x 25.4
36.4 x 714 x 803
831
Air Filter
Material
Polypropelene
Type
One-Touch
Item
Unit
Power Source (Phase, Voltage, Cycle)
ø
Single
V
220 - 230
Hz
50
Input Power
W
Cooling; 2.21k (215 ~ 2.54k)
Heating; 2.10k (245 ~ 2.75k)
Starting Current
A
9.7
Running Current
A
Cooling; 10.4 - 9.9
Heating; 9.7 - 9.3
Power Factor
%
Cooling; 97 - 97
Heating; 98 - 98
Power factor means total figure of compressor, indoor fan motor and outdoor fan motor.
*Maximum over current protection
A
12.6
Power Cord
Number of core
Length
m
Thermostat
Electronic Control
Protection Device
Electronic Control
ITEM
UNIT
INDOOR UNIT
OUTDOOR UNIT
Page of 63