CS-C75KE, CS-C95KE, CS-C125KE, CU-C75KE, CU-C95KE, CU-C125KE - Panasonic Air Conditioner Service Manual (repair manual). Page 17

Read Panasonic CS-C75KE / CS-C95KE / CS-C125KE / CU-C75KE / CU-C95KE / CU-C125KE Service Manual online

Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Saved Control
Starting Current Control
Anti-Freezing Control
  • 
If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
  • 
Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
8 Operation Details
8.1. Cooling Mode Operation
  • 
When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
  • 
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
  • 
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
  • 
When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.
  • 
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
s
T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
17
CS-C75KE CU-C75KE / CS-C95KE CU-C95KE / CS-C125KE CU-C125KE
Page of 88
Display

Click on the first or last page to see other CS-C75KE / CS-C95KE / CS-C125KE / CU-C75KE / CU-C95KE / CU-C125KE service manuals if exist.