8.4. Operation Control
(For 8.4.1. to 8.4.7. information applies only to Cooling and Soft Dry Operation)
8.4.1. Restart Control (Time Delay Safety Control)
 • When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
 − Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
 − Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
 • If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
 • This phenomenon is to balance the pressure inside the refrigerant cycle.
8.4.2. 7 Minutes Time Save Control
 • The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
 • This phenomenon is to reduce the built up humidity inside a room.
8.4.3. 60 Seconds Forced Operation
 • Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake
air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
 • The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
8.4.4. Anti-Freezing Control
 • If the temperature of the indoor heat exchanger falls below 2°C continuously for 4 minutes or more, the compressor turns off.
The fan speed setting remains the same.
 • This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form
returning to the compressor.
 • Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
 • Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.