CS-A9CKPG, CU-A9CKP6G, CS-A12CKPG, CU-A12CKP6G (serv.man2) - Panasonic Air Conditioner Service Manual Supplement (repair manual). Page 15

Read Panasonic CS-A9CKPG / CU-A9CKP6G / CS-A12CKPG / CU-A12CKP6G (serv.man2) Service Manual Supplement online

Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Starting Current Control
Anti-Freezing Control
  • If the temperature of the indoor heat exchanger falls
continuously below 2°C (35.6°F) for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
  • Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (50°F) (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
8 Operation Details
8.1. Cooling Mode Operation
  • When the compressor is stopped by Remote Control, it restarts after 3 minutes when it is turned ON by Remote Control.
  • When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
  • The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
  • When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.
  • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C (36.5°F) or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
▲ T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.