2. Evacuation 
(All amount of refrigerant leaked)
• Procedure 
(1) Connect the vacuum pump to the center hose
of charge set center hose 
(2) Evacuation for approximately one hour.  
–  Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).  
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump. 
–  Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed. 
Lo
Open
Open
Vacuum pump
3-Way
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
CLOSE
OPEN