AY-X08 (serv.man19). Procedure to check that gas and dust sensors are working correctly. - Sharp Air Conditioner Technical Bulletin (repair manual). Page 2

Read Sharp AY-X08 (serv.man19) Technical Bulletin online

AIR2003 10 01
Month of Issue:  
October 2003
        
Classification: 
White
TECHNICAL BULLETIN
Page 2 of 3
Sharp Electronics (UK) Limited
Reference -  ARCN-0302-01 a
Revision  - 1
White – Carry out as required
Yellow – Carry out as required and whenever the unit comes in for service
 Red – Carry out on all units
ACTION To check that the gas sensor is working correctly, follow the procedure outlined below:
1.  Remove power from the unit.
2.  Open the front panel of the indoor unit.
3.  Disconnect the wire connected from terminal 2 to the outdoor unit, and insulate the
end.  If this wire is not disconnected the outdoor unit could switch on intermittently.
4.  Apply power to the unit and at the same time push the AUX switch. A tone will
sound twice.
5.  Push AUX switch four times.  Some numbers will appear on the display.
6.  Use a cigrette lighter to discharge some gas into the latticed inlet for the gas
sensor.  DO NOT light the gas.
7.  Check the numbers indicated on the display.  If the value of the numbers on the
display goes up, the sensor is working.
            Position of the wire connected to terminal 2