AY-X08 (serv.man10). Breakdown diagnosis procedure - Sharp Air Conditioner Service Manual (repair manual). Page 2

Read Sharp AY-X08 (serv.man10) Service Manual online

28
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
Note:
1.
Normal : Only the timer lamp blinks. Error : Displayed by blinking of run
               lamp (above table).
2.
If the power plug is removed from the outlet or the breaker is switched to
               "OFF", the self-diagnostic memory will be erased.
3.
Example of outdoor unit LED 1 blinking :
: Blinks at 2-second intervals
: OFF
: ON
: Blinks 3 times at 0.2-second intervals
The error of indoor unit
Display by indoor unit operation lamp
Displayed in a pattern which comes on at  the same 
time as the timer lamp
4 seconds off
What to check, procedure
Display by 
outdoor 
unit lamp 
LED 1
Diagnosis
Solution
Condition 
of indoor 
and 
outdoor 
unit
Serial short
Serial open
1. Check the wiring between units.
1. Check the wiring between units.
1. Check the wiring between units.
2. Check the fuse in the outdoor unit.
3. Indoor control board.
4. Outdoor control board.
1. Rewire.
1. Rewire.
Indoor fan out of order
1. Is the fan motor locked ?
2. Is the wiring connector firmly fitted ?
3. Is the speed signal applied to the motor ?
Outdoor power supply  
does't turn on.
Wiring mistake.
1. Rewire.
2.
Replace the fuse, replace the 
outdoor board assembly.
3. Replace the board.
4. Replace the board.
1. Replace fan motor
2. Reattach.
3.
Replace the indoor control board 
assembly.
1
sec.
1
sec.
0.6
sec.
1
sec.
1
sec.
1
sec.
1
sec.
1
sec.
1
sec.
Overheat of the compressor
0.6
sec.
1
sec.
0.6
sec.
1
sec.
0.6
sec.
2 times
OFF
ON
OFF
Page of 3
Display