AY-AP24 (serv.man8). Troubleshooting - Sharp Air Conditioner Service Manual (repair manual). Page 3

Read Sharp AY-AP24 (serv.man8) Service Manual online

AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
20
For AY-AP18CS / AE-A18CS
The room is not cooled at all
or not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
The control circuit is normal.
   The compressor may be defective.
   The running capacitor may be defective.
   Refrigerant may be leaked.
   The outdoor fan motor may be defective.
   The outdoor fan motor capacitor may be defective.
Push the button "AUX." on 
the  indoor unit, for more than 5 sec.
Is the voltage
between terminal "N" and
"1" of the terminal board the
power supply voltage ?
Are the resistances
conformed Fig. 1 ?
Replace the thermistor ass'y with a new one.
NO
YES
YES
NO
Replace the PWB ass'y with a new one.
Fig. 1
Using a tester, measure voltage at
the terminals on the terminal board.
100
80
60
40
20
0
-10
0
10
20
30
40
Resistance
Thermistor
Room temperature
Heat exchange
Color
Yellow
Orange
To measure the resistance, first remove 
the connector as shown at right.
Room temperature 
thermistor TH1
Tester
Connector
No. 3 to 4
No. 1 to 2
Fig. 1 Temperature properties of  indoor thermistors
K
Heat exchange thermistor 
TH2 (orange)
25
°C resistance 15 K 
Room temperature 
thermistor TH1 (yellow)
25
°C resistance 10 K
Heat exchange 
thermistor TH2
Tester
4
1 CN4
Page of 5