AY-AP24 (serv.man12) - Sharp Air Conditioner Service Manual (repair manual). Page 11

Read Sharp AY-AP24 (serv.man12) Service Manual online

11
AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
FUNCTIONS
1.
Temperature control characteristic
1-1
COOL operation
In the “COOL” mode, the thermostat circuit is
controlled by five thermostat lines (C1 thru C5).
Figure Y-1
1-2
DRY operation
In the “DRY” mode, the thermostat circuit is
controlled by three thermostat lines (D1 thru D3).
Figure Y-2
1-3
HEAT operation
In the “HEAT” mode, the thermostat circuit is
controlled by six thermostat lines (H01 thru H4).
Figure Y-3
2.
Operation modes
2-1
COOL operation
The compressor turns on or off, at the thermostat
lines C3 and C4. The outdoor fan motor is also
controlled with the compressor.
18
32
C1
C2
C3
C4
17.5
18.5
19.5
19.0
20.5
31.5
33.0
32.5
33.5
34.5
Preset temperature (˚C)
Room temperature (˚C)
C5
Room temperature(˚C)
Preset temperature (˚C)
18
32
D1
D2
D3
17.5
18.5
19.5
31.5
32.5
33.5
Preset temperature (˚C)
H4
H3
H2
H1
H02
H01
17.5
18.5
20
21
22
23
31.5
32.5
34.0
35.0
36.0
37.0
18
32
Room temperature(˚C)
Room temperature
Preset temperature
Room 
temperature
transition
C4
C5
States 1 & 3 : Compressor ON
State 2 : Compressor OFF
1
2
3
Figure Y-4
Page of 44
Display

Click on the first or last page to see other AY-AP24 (serv.man12) service manuals if exist.