AY-A244 - Sharp Air Conditioner Specification (repair manual). Page 20

Read Sharp AY-A244 Specification online

20
AY-A184E
AY-A244E
AE-A184E
AE-A244E
For AY-A184E/AE-A184E
The room is not cooled at all
or not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
The control circuit is normal.
   The compressor may be defective.
   The running capacitor may be defective.
   Refrigerant may be leaked.
   The outdoor fan motor may be defective.
   The outdoor fan motor capacitor may be defective.
Push the button "TEST RUN" on  
the indoor unit, and wait 3 minutes.
Is the voltage
between terminal "N" and
"1" of the terminal board the
power supply voltage ?
Are the resistances
conformed Fig. 1 ?
Replace the thermistor ass'y with a new one.
NO
YES
YES
NO
Replace the PWB ass'y with a new one.
0
20
40
60
80
100
120
140
160
180
K
0
10
20
30 40˚C
-10
CHARACTERISTIC OF TH1 & TH2
Fig. 1
10˚C
30K 
Using a tester, measure voltage at
the terminals on the terminal board.
Page of 44
Display

Click on the first or last page to see other AY-A244 service manuals if exist.