The room is not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
The control circuit is normal.
   The compressor may be defective.
   The running capacitor may be defective.
   Refrigerant may have leaked.
   The outdoor fan motor may be defective.
   The outdoor fan motor capacitor may be defective.
Push the button "TEST" on the 
indoor unit, and wait 3 minutes.
Is there a  voltage
between terminal "N" and
"1" of the terminal board the
power supply voltage ?
Are the resistances
correct Fig. 1 ?
Replace the thermistor ass'y with a new one.
NO
YES
YES
NO
Replace the PWB ass'y with a new one.
0
20
40
60
80
100
120
140
160
180
0
10
20
30 40˚C
-10
CHARACTERISTIC OF TH1 & TH2
Fig. 1
Using a meter, measure voltage at
the terminals on the terminal board.
K
10˚C
30K
Page of 28