AH-AP24 (serv.man8). Troubleshooting guide of control circuit - Sharp Air Conditioner Service Manual (repair manual). Page 5

Read Sharp AH-AP24 (serv.man8) Service Manual online

31
AH/AY-AP18DR
AH/AY-AP24DR
For AY-AP24DR/AE-A24DR, AY-AP18DR/AE-A18DR
The room is not heated at all or not heated.
The compressor does not operate.
The control circuit board is normal.
   Refrigerant may be leaked.
   The running capacitor may be defective.
   The outdoor fan motor may be defective.
   The outdoor fan motor capacitor may be defective.
   The compressor may be defective.
   The thermistor may be defective.
   
   
Is the voltage
between terminal "N" and
"4"("1" ..... AY-AP18DR) of the 
terminal board the power 
supply voltage ?
NO
Replace the PWB ass'y with a new one.
Push the button of "AUX" on the  indoor 
unit, for more than 5 sec.
Using a tester, measure voltages at the 
terminals on the terminal board.
Select HEAT MODE with remote controller.
And then start operation.
Is the voltage
between terminal "N" and
"2" of the terminal board the
power supply voltage ?
Is the voltage
between terminal "N" and
"3" of the terminal board the
power supply voltage ?
YES
YES
YES
NO
NO
Page of 5
Display

Download Sharp AH-AP24 (serv.man8) Service Manual (Repair Manual)