AE-XM24CR (serv.man10). Breakdown diagnosis procedure - Sharp Air Conditioner Service Manual (repair manual). Page 2

Read Sharp AE-XM24CR (serv.man10) Service Manual online

44
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
: Blinks at 1-second intervals
: OFF
: ON
: Blinks 3 times at 0.1-second intervals
Indoor and outdoor unit 
completely stopped
Display by indoor unit operation lamp
Displayed in a pattern which comes on at  the 
same time as the timer lamp
4 seconds off
What to check, procedure
Display by 
outdoor 
unit lamp 
LED 
51 ~ 52
Diagnosis
Solution
Condition 
of indoor 
and 
outdoor 
unit
5 times
6 times
7 times
AC overcurrent error
1. Is the discharge outlet of the outdoor unit clogged ?
1. Clear the discharge outlet.
8 times
Abnormal wire check
1. Check the attached point CN8B of outdoor unit.
2. Measure the resistance value of thermistor TH5, TH6, TH7 
    of outdoor unit.
3. Check the expansion valve. (unit A, unit B, unit C)
4. 
Are four expansion valves connected by mistake ?
5. Check the wiring between units.
1.Reattach
2.Replace the outdoor thermistor 
assembly. (TH5, TH6, TH7)
3.Replace the outdoor control 
board assembly.
4. Reattach
5. Check the wiring between units.
6. Check the incorrect wiring.
 
 
(When connection between the   
units is wrong as follows)
1.Replace Power module (IPM)
2.Replace the outdoor Power 
supply P.W.B..
3.Rewire
1.Replace Power factor module 
(AF1)
1.Replace the outdoor control 
board assembly (Current 
transformer is broken.) 
1.Reattach.
2.
Replace the outdoor thermistor 
assembly. (RTHM-A022JBE0)
   or (RH-HXA024JBZZ or  
RH-HXA022JBZZ )
1. Can voltage be detected at the current transformer on the 
outdoor unit control board?
1. Are the connectors of the outdoor unit thermistors well   
attached ?
2. Measure the resistance of thermistors TH1, TH2, TH3, 
TH4, TH5, TH6, TH7 on the outdoor unit (see Figure 2).
AC abnormal current  
error
Open circuit of the 
thermistor error
A
B
Indoor unit
Outdoor unit
UNIT A
UNIT B
C
UNIT C
(Example)
Terminal 
board
9 times
Rotation error of the
compressor
1. Check the voltage (18V) between BCN14  3   and   4
2. Check the compressor terminal and Power module terminal
    RED : S(COMP), U(IPM), WHITE : C(COMP), V(IPM), 
    ORANGE : R(COMP), W(IPM)
11 times
Power factor module
(AF1) error
1. Check the resistance value among the terminal of the 
    power factor module (L - and OUT -)
Page of 4