FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES
Function
NO
Description
Detection 
time
Restart 
condition
Restart 
times
Indoor Outdoor
Operation
Self diagnostic
display
1
2
3
4
5
6
7
Indoor fan 
lock
Indoor fan 
rpm error
Indoor 
freezing 
guard
Indoor 
overheating 
control
DC 
overcurrent
AC 
overcurrent
Compressor 
overheating 
control
Compressor 
high 
temperature 
error
Stops operation if no revolution pulse 
signal is input from the indoor fan motor for 
one minute.
Stops operation if the revolution pulse 
signal from the indoor fan indicates low 
rpm (approximately 300 rpm or less).
Lowers the operating frequency if the 
temperature of the indoor heat exchanger 
goes below 5
°
C during cooling. Stops the 
compressor if the temperature stays below 
0
°
C for 4 minutes.
Lowers the operating frequency if the 
temperature of the indoor heat exchanger 
rises above the overheating temperature 
during heating. Stops the compressor if the 
temperature stays above the overheating 
temperature for 1 minute at minimum 
frequency or less.
Set values for overheating temperature
During normal operation: 45
°
C to 54
°
C
During full power operation: 47
°
C to 
58
°
C
Stops the compressor if a current of 
approximately 23A or more flows in the 
power transistor module. 
Lowers the operating frequency if the 
compressor AC current exceeds 
set value(   ).Show "2-2(1)AC peak control"
Stops the compressor if the current 
exceeds at 40Hz or less set value(   ).
Lowers the operating frequency if the 
temperature of the compressor chamber 
thermistor (TH1) rises above 105
°
C.
Stops the compressor if the thermistor 
stays above 105
°
C for 1 minutes at 
minimum frequency or less.
Stops the compressor if the compressor 
chamber thermistor is above 114
°
C.
(Or when TH1 shorts)
When indoor 
fan is revolving
During cooling 
and dry 
During heating
During 
compressor 
operation
During 
compressor 
operation
During 
compressor 
operation
During 
operation
Operation OFF
Automatically 
restarts when the 
exchange 
temperature rises 
above the freezing 
prevention 
temperature (above 
2
°
C)
Automatically 
restarts when the 
exchange 
temperature goes 
below the 
overheating 
temperature.
Automatically 
restarts after safety 
time (170 seconds) 
Automatically 
restarts after safety 
time (170 seconds)
Automatically 
restarts after safety 
time (170 seconds)
Automatically 
restarts when 
thermistor (TH1) 
temperature falls 
below 100
°
(approximately 30 
minutes)
No limit
No limit
No limit
8times
4 times
No limit
4 times
Yes
No
No
Yes
Yes
No
Yes
No
No
No
Yes
Yes
No
Yes
(   )
M o d e l
S e t  
v a l u e
C o o l
H e a t
6 . 2 A
6 . 7 A
5 . 3 A
5 . 4 A
7 . 9 A
1 0 . 5 A
5 . 3 A
6 . 2 A
7 . 9 A
A E - X 0 8 C R
A E - X 1 0 C R
A E - X 1 3 C R
A U - X 0 8 C R
A U - X 1 0 C R
A U - X 1 3 C R
26
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
Function
NO
Description
Detection 
time
Restart 
condition
Restart 
times
Indoor Outdoor
Operation
Self diagnostic
display
8
9
10
11
12
13
14
15
16
Outdoor heat 
exchanger
overheating 
control
Outdoor 
thermistor 
short
Outdoor 
thermistor 
open
AC abnormal 
current error
Serial signal 
error
Power factor 
module
(Active filter) 
error
Rotation error
of the 
compressor
Open circuit 
of the power 
module (IPM) 
heat-sink 
thermistor
Overheat of 
the power 
module (IPM) 
or short 
circuit of the 
power 
module (IPM) 
heat-sink 
thermistor
Lowers the operating frequency if the 
temperature of the outdoor heat exchanger 
rises above 55
°
C during cooling. Stops the 
compressor if the temperature stays above 
55
°
C for 1 minute at minumum frequency.
Stops the compressor if an outdoor 
thermistor (excluding TH1) shorts.
Stops the compressor if the circuit of an 
outdoor thermistor breaks.
Stops the compressor if if the operating 
frequency is above 50 Hz and the 
compressor current is below 1.0 A.
Turns the compressor relay off if the indoor 
unit does not receive a serial signal from 
the outdoor unit for 8 minutes.
Stops the compressor if the outdoor unit 
does not receive a serial signal from the 
indoor unit for 30 seconds.
When an power factor module error input 
is detected.
When abnormalities occur to a position 
detected signal.
Stops the compressor if the circuit of the 
heat-sink thermistor.
Stops the compressor if the temperature of 
the power module is (IPM) is exceeds 
90˚C. Also stops the compressor if the 
heat-sink thermistor shorts.
During 
compressor 
operation
When 
compressor is 
activated
When 
compressor is 
activated
During 
compressor 
operation
During 
operation
During 
operation
During 
compressor 
operation
Under feedback 
operation of 
compressor 
operation
When 
compressor is 
activated
During 
compressor 
operation
Automatically 
restarts after safety 
time (170 seconds)
Automatically 
restarts after safety 
time  (170 seconds)
Automatically 
restarts after safety 
time  (170  seconds)
Automatically 
restarts after safety 
time  (170 seconds)
Automatically 
restarts less than 8 
minutes after 
operation stops
Restarts after 
reception of serial 
signal
Automatically 
restarts after safety 
time  (170 seconds)
Automatically restart 
after safety time 
(170 seconds)
Automatically 
restarts after safety 
time (170 seconds)
Automatically 
restarts after safety 
time (170 seconds)
No limit
4 times
4 times
4 times
No limit
No limit
4 times
8 times
4 times
4 times
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Page of 2
Display

Download Sharp AE-X08 (serv.man9) Service Manual (Repair Manual)

Here you can read online and download Sharp AE-X08 (serv.man9) Service Manual in PDF. AE-X08 (serv.man9) service manual will guide through the process and help you recover, restore, fix, disassemble and repair Sharp AE-X08 (serv.man9) Air Conditioner. Information contained in service manuals typically includes schematics / circuit diagrams, wiring diagrams, block diagrams, printed wiring boards, exploded views, parts list, disassembly / assembly, pcb.