33
AH/AY-AP18DR
AH/AY-AP24DR
Cycle temperature and service port pressure
ISO condition
Dimension of Capillary tube
Cycle temperature and service port pressure
ISO condition
Dimension of Capillary tube
Indoor side
Outdoor side
Temperature (˚C)
Temperature (˚C)
Relative humididity (%)
Relative humididity (%)
27
47
35
40
Cooling
20
-
7
87
Heating
Indoor side
Outdoor side
Temperature (˚C)
Temperature (˚C)
Relative humididity (%)
Relative humididity (%)
27
47
35
40
Cooling
O.D.
I.D.
L
Capillary tube 
ø 3.2
ø 1.8
600
O.D.
I.D.
L
Capillary tube 
ø 3.5
ø 2.0
700
For AH-AP18DR
For AH-AP24DR
Cooling
Heating
NO. Condition
Model
AY-AP18DR
1
2
3
4
Service port guage pressure
85˚C
79˚C
42˚C
2˚C
12˚C
39˚C
9˚C
-3˚C
0.89MPa
2.65MPa
Cooling
Heating
AY-AP24DR
85˚C
84˚C
42˚C
2˚C
11˚C
39˚C
7˚C
-2˚C
0.76MPa
3.2MPa
Based on 'ISO 5151:1994(E),condition T1'
(at 220V refrigerant pipes length 7.5m)
Cooling
Cooling
NO. Condition
Model
AH-AP18DR
1
2
3
4
Service port guage pressure
80˚C
86˚C
43˚C
43˚C
12˚C
11˚C
7˚C
7˚C
0.89MPa
0.77MPa
AH-AP24DR
Based on 'ISO 5151:1994(E),condition T1'
(at 220V refrigerant pipes length 7.5m)
O.D.
I.D.
L
Capillary tube A
ø 3.2
ø 1.8
700
Capillary tube C
(Upper  row)
  
ø 2.7
ø 1.6
150
Capillary tube B
ø 3.2
ø 1.8
300
Capillary tube D
(Lower  row)
  
ø 2.7
ø 1.6
150
O.D.
I.D.
L
Capillary tube A
ø 3.2
ø 2.0
500
Capillary tube B
ø 3.2
ø 2.0
700
Capillary tube C
(Upper  row)
ø 2.7
ø 1.6
150
Capillary tube D
(Lower  row)
ø 2.7
ø 1.6
244
For AY-AP18DR
For AY-AP24DR
Page of 2