12.19  Boiler Bivalent Control 
-  Boiler is an additional or alternative heat source to heat up the room when necessary. 
-  Purpose of this control is to turn ON and turn OFF the Boiler output signal when boiler heating capacity 
needed in the system. 
-  Boiler is possible to connect to DHW Tank and Buffer Tank depends on the installer. 
-  Boiler operation parameter need to be set on Boiler itself, indoor do not control the boiler operation direction 
and operation. 
-  There are Alternative mode, Parallel mode, & Advance Parallel mode available to select by installer to fit to 
the total system. 
Bivalent control selection by remote controller 
 
Remote control setting value: 
1)  Outdoor Ambient Set = (Range: -15°C ~ 15°C) 
 
a) Alternative 
Mode 
-  Only one heat source operates at one time, either heat pump or boiler depends on condition. 
Control detail: 
During Operation ON at Heat mode or Tank mode or Heat + Tank Mode 
-  Boiler signal turn ON and heat pump and water pump turn OFF when: 
a.  Outdoor ambient < Outdoor Ambient Set AND 
b.  Boiler prohibit flag = 0 
** However indoor water pump can operate when Anti-freeze control condition fulfilled. 
 
-  Boiler signal turn OFF and heat pump and water pump turn ON when: 
a.  Outdoor ambient > Outdoor Ambient Set + [2°C] OR 
b.  Boiler prohibit flag = 1 
 
b) Parallel 
Mode 
-  Parallel mode allows heat pump and boiler ON at the same time. Boiler operates as an additional heating 
capacity when low heat pump capacity at low ambient condition. 
Control detail: 
During operation ON at Heat mode or Tank mode or Heat + Tank mode 
-  Boiler signal turns ON when: 
a.  Outdoor ambient < Outdoor Ambient Set AND 
b.  Boiler prohibit flag = 0 
-  Boiler signal turns OFF when: 
a.  Outdoor ambient > Outdoor Ambient Set + [2°C] OR 
b.  Boiler prohibit flag = 1 
 
c)  Advance Parallel Mode 
-  Advance parallel mode allow heat pump to operate and turn ON boiler only when ambient and temperature 
condition is fulfilled. 
Remote control setting value: 
1)  Outdoor Ambient Set = (Range : -15°C ~ 15°C)  
2)  Selection of boiler connection direction. (Heat only, DHW only, Heat & DHW) 
3)  Setting data under Heat Direction 
a.  Start Temperature 
| START_TEMP | 
b.  Start Delay Timer 
| START_TIMER | 
c.  Stop Temperature 
| STOP_TEMP | 
d.  Stop Delay Timer 
| STOP_TIMER | 
4)  Setting data under DHW Direction 
a.  Delay Timer 
| DELAY_TIMER | 
 