WH-SXC09H3E5, WH-SXC12H6E5, WH-UX09HE5, WH-UX12HE5 - Panasonic Air Conditioner Service Manual (repair manual). Page 11

Read Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual online

11 
Item 
Unit 
Outdoor Unit 
Type  
Hermetic 
Motor 
Motor Type 
 
Brushless (4-poles) 
Compressor 
Rated Output 
kW 
3.00 
Type  
Propeller 
Fan 
Material  
PP 
Motor Type 
 
DC (8-poles) 
Input Power 
— 
Output Power 
60 
Fan 
Fan Speed 
rpm 
Cooling: 600 (Top), 640 (Bottom) 
Heating: 520 (Top), 560 (Bottom) 
Fin material 
 
Aluminium (Pre Coat) 
Fin Type 
 
Corrugated Fin 
Row × Stage × FPI 
 
2 × 51 × 18 
Heat Exchanger 
Size (W × H × L) 
mm 
903.7 × 1295.4 × 38.1 
ø Single 
V 230 
Power Source (Phase, Voltage, Cycle) 
Hz 50 
Condition 
(Ambient/Water) 
A35W7 A7W35 A2W35 
Input Power 
kW 
Cooling: 3.56 
Heating: 2.53 
Heating: 3.49 
Maximum Input Power For Heatpump System 
kW 
6.27 
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
1Ø / 29.0 / 6.27k 
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
1Ø / 26.0 / 6.00k 
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
— / — / — 
Starting Current 
16.5 
Condition 
(Ambient/Water) 
A35W7 A7W35 A2W35 
Running Current 
Cooling: 16.5 
Heating: 11.7 
Heating: 16.1 
Maximum Current For Heatpump System 
29.0 
Power Factor 
Power factor means total figure of compressor and 
outdoor fan motor. 
Cooling: 94 
Heating: 94 
Heating: 94 
Number of core 
 
— 
Power Cord 
Length m 
(ft) 
— 
Thermostat  
Electronic 
Control 
Protection Device 
 
Electronic Control 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127
Display