Control Content: 
  External room thermostat control activate only when remote thermostat connection select YES by Indoor control 
panel. 
  When indoor running heat mode, refer thermo On/Off from heating line feedback. And when indoor running cool 
mode, refer thermo On/Off from cooling line feedback. 
  Heat pump Off immediately when receive thermo off feedback. 
12.20 Three Ways Valve Control 
Purpose: 
- 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side. 
 
Control contents: 
1  3 ways valve switch Off: 
During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side. 
2  3 ways valve switch On: 
During 3 ways valve switch On time, the hot water will provide heat capacity to tank side. 
3 Stop 
condition: 
During stop mode, 3 ways valve will be in switch off position. 
 
L
N2
Indoor Unit
N1
Spring Return 2 point
SPDT 3 wire
3
5
M
L
1
N1
3
N2
COM
Open
Close
5
6: Terminal Board No.
M
L
NC
1
N1
3
N2
5
M
L
NO
1
N1
3
N2
5
1
AC230V
 
 
* During pump down and force mode, fix 3 ways valve in close condition. 
 
* Recommended Parts : SFA 21/18 (Siemens) 
12.21 Two Ways Valve Control 
Functionality of 2 ways valve: 
  Use to allow hot water to floor heating panel or block cold water to floor heating panel. 
 
Control contents: 
1  When indoor running in heat mode, OPEN the 2 ways valve. 
2  When indoor running in cool mode, CLOSE the 2 ways valve. 
3 Stop 
condition: 
a. 
During stop mode, fix 2 ways valve in close condition. 
 
L
N2
Indoor Unit
N1
Spring Return 2 point
SPDT 3 wire
3
5
M
L
1
N1
3
N2
COM
Open
Close
5
3: Terminal Board No.
M
L
NC
1
N1
3
N2
5
M
L
NO
1
N1
3
N2
5
1
AC230V
 
 
* During pump down mode, fix 2 ways valve in close condition. 
* During force mode, open 2 ways valve. 
 
* Recommended Parts : SFA 21/18 (Siemens) 