Item 
Unit 
Outdoor Unit 
Refrigeration Charge Less 
m (ft) 
10 (32.8) 
Compressor 
Type 
 
Hermetic Motor 
Motor Type 
 
Brushless (4-poles) 
Rated Output 
kW 
1.70 
 Fan 
 Type 
 
Propeller Fan 
 Material 
 
PP 
 Motor Type 
 
DC (8-poles) 
 Input Power 
W 
 Output Power 
W 
60 
 Fan Speed 
rpm 
Cooling: 670 
Heating: 570 
 Heat Exchanger 
 Fin material 
 
Aluminium (Pre Coat) 
 Fin Type 
 Corrugated 
Fin 
 Row × Stage × FPI 
 
2 × 30 × 17 
 Size (W × H × L) 
mm 
38.1 × 762.0 × 873.8 : 903.8 
Power Source (Phase, Voltage, Cycle) 
ø Single 
V 230 
Hz 50 
Input Power 
Condition 
(Ambient/Water)
A35W7 A7W35 A2W35 
kW 
Cooling: 2.28 
Heating: 1.57 
Heating: 1.96 
Maximum Input Power For Heatpump System 
kW 
4.59 
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
1Ø / 21.0 / 4.59k 
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
1Ø / 13.0 / 3.00k 
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
- / - / - 
Starting Current 
7.2 
Running Current 
Condition 
(Ambient/Water)
A35W7 A7W35 A2W35 
Cooling: 10.3 
Heating: 7.2 
Heating: 9.0 
Maximum Current For Heatpump System 
21.0 
Power Factor 
Power factor means total figure of compressor and 
outdoor fan motor. 
Cooling: 96 
Heating: 95 
Power Cord 
Number of core 
 
Length m 
(ft) 
Thermostat  
Electronic 
Control 
Protection Device 
 
Electronic Control 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127