12.16 Anti Freeze Control 
  Anti freeze protection control menu can be set YES or NO by control panel. 
  In heatpump system, there are 3 types of anti freeze control: 
1.  Expansion tank anti-freeze control 
  Expansion tank anti freeze heater ON condition: 
o  Outdoor ambient temp. < 3°C 
  Expansion tank anti freeze heater OFF condition: 
o  Outdoor ambient temp. > 4°C 
 
2.  Water pump circulation anti freeze control 
  Water pump turns ON when ALL below conditions are fulfilled: 
o  Heatpump OFF (stand by) OR error occurs. 
o  Water flowing flag is ON. 
o  Water flow switch is not abnormal. 
o  Outdoor ambient temp. < 3°C OR outdoor ambient temp. sensor is abnormal. 
o  Water inlet/outlet temp. < 6°C. 
o  After 5 minutes from previous water pump OFF. 
  Water pump turn OFF when ANY of below conditions is fulfilled: 
o  Outdoor ambient temperature ≥ 4°C. 
o  During -5°C < outdoor ambient temp. < 4°C 
  After water pump ON for 4 minutes, and water inlet temp. ≥ 8°C. 
  Else, shift to back up heater anti freeze control. 
o  During outdoor ambient temp. < -5°C 
  After water pump ON for 4 minutes, and water inlet/outlet ≥ 20°C. 
  Else, shift to back up heater anti freeze control. 
  However, if flow switch is abnormal (H62), then water pump circulation anti freeze control will not activate. 
 
3.  Back up heater anti freeze control: 
  Back up heater turn ON when ALL below conditions is fulfilled: 
o  Water inlet/outlet temp. < 6°C. 
o  Water pump circulation anti freeze control activated and water pump ON for 4 minutes. 
  Back up heater turns OFF when ANY of below conditions is fulfilled: 
o  Water inlet/outlet temp. > 28°C. 
o  Water pump circulation anti freeze control deactivated/water pump OFF. 
  However, if back up heater is abnormal (H70) then back up heater anti freeze control will not activate. 
12.16.1  Zone Anti-Freeze Control 
  If buffer tank selection is “NO” and Anti- Freeze function select “NO” from remote control, this control cannot 
activate. 
 
Start condition: 
  After [5] min from previous Zone pump off. AND 
  Outdoor air temp < [3] °C OR Outdoor sensor is abnormal. AND 
  Zone water temperature < [6]°C OR Zone Sensor Short or Open 
 
Cancel condition: 
  After water Zone pump ON [4] min AND 
  Outdoor air temp ≥ [4]°C OR 
  During -5 °C ≤ Outdoor air temp < [4] °C OR 
Zone water temperature sensor > [8] °C 
  During Outdoor air temp < [-5] °C 
Zone water temperature sensor > [20] °C 
*However, Zone water temperature sensor is Open or Short, Condition C and D is ignored. 
 
 
 
 
 
 
 
 
 