16.5.28 Indoor Water Outlet Temperature Sensor 2 Abnormality (F30)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet
temperature sensor 2 are used to determine sensor error.
temperature sensor 2 are used to determine sensor error.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty sensor.
3. Faulty indoor unit PCB.
2. Faulty sensor.
3. Faulty indoor unit PCB.
Abnormality Judgment:
Continue for 5 seconds.