1-1-5-4
1
1
Simultaneous (Double-Twin) -Type
1-1.  Unit Specifications
PE1
5. Ducted Type S-36PN1E5B×4 / U-125PE1E5A
INDOOR
MODEL
S-36PN1E5B×4
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-125PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5
12.5
12.5
-
-
-
3.3
14.0 
BTU/h
42700
42700
42700
-
-
-
11300
47800
Current
A
0.42×4
0.43×4
0.44×4
16.8
16.3
15.7
-
-
Input power
W
90×4
95×4
100×4
3.530k
3.510k
3.490k
-
-
TOTAL W
-
3.890k
3.890k
3.890k
960
4.860k
Annual consumption
TOTAL kWh *
4
-
-
1945
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.21
3.21/A
3.21
3.44
2.88
Erp
*
6
Pdesign
kW
-
-
-
-
12.5
-
-
-
η 
s,c
%
-
-
-
-
266.5
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
96 
94 
93 
-
-
Noise indoor
dB-A (H/M/L)
35/33/30
-
-
-
Power Level dB
57/55/52
-
-
-
Noise outdoor
dB-A  (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0 
14.0 
14.0 
-
-
-
4.1 
16.0 
BTU/h
47800
47800
47800
-
-
-
14000
54600
Current
A
0.42×4
0.43×4
0.44×4
16.6
16.1
15.6
-
-
Input power
W
90×4
95×4
100×4
3.520k
3.500k
3.480k
-
-
TOTAL W
-
3.880k
3.880k
3.880k
1.160k
5.360k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.61
3.61/A
3.61
3.53
2.99
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5 
-
-
-
Tbivalent
°C
-
-
-
-
-7 
-
-
-
η 
s,h
%
-
-
-
-
145.7 
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
elbu(-10°C)
kW
-
-
-
-
2.38
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
96 
95 
93 
-
-
Noise indoor
dB-A (H/M/L)
35/33/30
-
-
-
Power Level dB
57/55/52
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A)  /  Max Input power(W)
0.60×4/130×4 0.62×4/140×4 0.63×4/150×4 28.0/6.000k
28.0/6.200k
28.0/6.400k
-
Starting current(A)/Comp output(W)
-
-
-
16.8/3.0k
16.3/3.0k
15.7/3.0k
-
Network Impedance(ΩMAX.)
-
-
Fan motor output (Indoor/Outdoor) W
60×4
90×2
-
Moisture removal volume
L/h(Pt/h)
7.9
 (1.9×4)
(16.6)
-
-
External static pressure
Pa
25 (MAX80)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
 14.0×4/12.0×4/10.0×4 (494)×4/(424)×4/(353)×4
-
-
-
Heating
m³/min (ft³/min)
 14.0×4/12.0×4/10.0×4 (494)×4/(424)×4/(353)×4
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
130.0
(4591)
-
-
Heating
m³/min (ft³/min)
-
110.0
(3885)
-
-
Refrigerant type  /  amount g(oz)
-
R410A
3.40k
(119.9)
-
  Product dimension
Height mm(inch)
250 (9-27/32)
1416 (55-3/4)
-
Width
mm(inch)
780 [+100] (30-45/64 [+3-15/16])
940 (37-1/32)
-
Depth
mm(inch)
650 (25-19/32)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
338 (13-5/16)
1556 
-
Width
mm(inch)
991 (39-1/64)
1055 
-
Depth
mm(inch)
761 (29-61/64)
485 
-
Weight
(NET)
kg(lb)
29 (64)
98 (216)
-
(GROSS)  kg(lb)
34 (75)
108 (238)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit  (actually)
5 (6) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
Max Working Pressure HP/LP Mpa (bar)
4.15/2.70 (41.5/27.0)
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference  m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1 : In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 :  If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall  
 be used.
*3 : Network Impedance shall be applicable for EUROPE and CHINA models. 
*4 : The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 : EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 :  
η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   4
19/09/26   17:01:42
Page of 127
Display

Click on the first or last page to see other U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B service manuals if exist.