U-50PE2E5A, U-100PE1E8A, U-100PEY1E8, U-125PE1E8A, U-125PEY1E8, U-140PE1E8A, U-140PEY1E8, S-100PU2E5B, S-125PU2E5B, S-140PU2E5B, S-71PU2E5B, S-100PF1E5B, S-125PF1E5B, S-140PF1E5B, S-71PF1E5B - Panasonic Air Conditioner Service Manual (repair manual). Page 121

Read Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual online

1-1-5-2
1
1
Simultaneous (Twin) -Type
1-1.  Unit Specifications
PE1
5. Ducted Type S-36PN1E5B×2 / U-71PE1E5A
INDOOR
MODEL
S-36PN1E5B×2
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-71PE1E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
7.1
7.1
7.1
-
-
-
2.5
8.0 
BTU/h
24200
24200
24200
-
-
-
8500
27300
Current
A
0.42×2
0.43×2
0.44×2
9.50
9.20
8.95
-
-
Input power
W
90×2
95×2
100×2
1.970k
1.960k
1.950k
-
-
TOTAL W
-
2.150k
2.150k
2.150k
610
2.790k
Annual consumption
TOTAL kWh *
4
-
-
1075
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.30
3.30/A
3.30
4.10
2.87
Erp
*
6
Pdesign
kW
-
-
-
-
7.1
-
-
-
SEER
(W/W)
-
-
-
-
5.3
-
-
-
Annual consumption
kWh
-
-
-
-
467
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
94
93
91
-
-
Noise indoor
dB-A (H/M/L)
35/33/30
-
-
-
Power Level dB
57/55/52
-
-
-
Noise outdoor
dB-A  (H/L)
-
48/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
8.00
8.00
8.00
-
-
-
2.0
9.0 
BTU/h
27300
27300
27300
-
-
-
6800
30700
Current
A
0.42×2
0.43×2
0.44×2
9.95
9.65
9.40
-
-
Input power
W
90×2
95×2
100×2
2.080k
2.070k
2.060k
-
-
TOTAL W
-
2.260k
2.260k
2.260k
500
2.960k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.54
3.54/B
3.54
4.00
3.04
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
6.2
-
-
-
Tbivalent
°C
-
-
-
-
-9
-
-
-
SCOP
(W/W)
-
-
-
-
3.8 
-
-
-
Annual consumption
kWh
-
-
-
-
2282 
-
-
-
elbu(-10°C)
kW
-
-
-
-
0.25
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
95 
93 
91 
-
-
Noise indoor
dB-A (H/M/L)
35/33/30
-
-
-
Power Level dB
57/55/52
-
-
-
Noise outdoor
dB-A (H/L)
-
50/-
-
-
Power Level dB
-
67/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A)  /  Max Input power(W)
0.60×2/130×2 0.62×2/140×2 0.63×2/150×2 18.0/3.800k
18.0/3.930k
18.0/4.060k
-
Starting current(A)/Comp output(W)
-
-
-
9.95/2.0k
9.65/2.0k
9.40/2.0k
-
Network Impedance(ΩMAX.)
-
-
Fan motor output (Indoor/Outdoor) W
60×2
90
-
Moisture removal volume
L/h(Pt/h)
4.2
 (2.1×2)
(8.8)
-
-
External static pressure
Pa
25 (MAX80)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
14.0×2/12.0×2/10.0×2 (494)×2/(424)×2/(353)×2 
-
-
-
Heating
m³/min (ft³/min)
14.0×2/12.0×2/10.0×2 (494)×2/(424)×2/(353)×2 
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
60.0
(2119)
-
-
Heating
m³/min (ft³/min)
-
60.0
(2119)
-
-
Refrigerant type  /  amount g(oz)
-
R410A
2.35k
(82.9)
-
  Product dimension
Height mm(inch)
250 (9-27/32)
996 (39-7/32)
-
Width
mm(inch)
780 [+100] (30-45/64 [+3-15/16])
940 (37-1/32)
-
Depth
mm(inch)
650 (25-19/32)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
338 (13-5/16)
1136 
-
Width
mm(inch)
991 (39-1/64)
1055 
-
Depth
mm(inch)
761 (29-61/64)
485 
-
Weight
(NET)
kg(lb)
29 (64)
69 (152)
-
(GROSS)  kg(lb)
34 (75)
77 (170)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit  (actually)
5 (6) 
2 (3)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
Max Working Pressure HP/LP Mpa (bar)
4.15/2.70 (41.5/27.0)
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 50m
(16.4 ~ 164.0)
-
Indoor unit & Outdoor unit height difference  m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1 : In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 :  If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall  
 be used.
*3 : Network Impedance shall be applicable for EUROPE and CHINA models. 
*4 : The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 : EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 :  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data   
 indicates in an attached sheet.