U-50PE2E5A, U-100PE1E8A, U-100PEY1E8, U-125PE1E8A, U-125PEY1E8, U-140PE1E8A, U-140PEY1E8, S-100PU2E5B, S-125PU2E5B, S-140PU2E5B, S-71PU2E5B, S-100PF1E5B, S-125PF1E5B, S-140PF1E5B, S-71PF1E5B - Panasonic Air Conditioner Service Manual (repair manual). Page 120

Read Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual online

1-1-5-1
1
1
Single -Type
1-1.  Unit Specifications
PE2
5. Ducted Type S-36PN1E5B / U-36PE2E5A
INDOOR
MODEL
S-36PN1E5B
-
-
PANEL
MODEL
-
-
-
OUTDOOR
MODEL
-
U-36PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN14825  /  EN12102
Power supply
Ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
3.6 
3.6 
3.6 
-
-
-
1.5 
4.0 
BTU/h
12300
12300
12300
-
-
-
5100
13600
Current
A
0.42 
0.43 
0.44 
4.35 
4.15 
3.95 
-
-
Input power
W
90
95
100
0.870k
0.865k
0.860k
-
-
TOTAL W
-
0.960k
0.960k
0.960k
340
1.120k
Annual consumption
TOTAL kWh *
4
-
-
480
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.75 
3.75/A
3.75 
4.41
3.57
Erp
*
6
Pdesign
kW
-
-
-
-
3.6 
-
-
-
SEER
(W/W)
-
-
-
-
4.6 
-
-
-
Annual consumption
kWh
-
-
-
-
269 
-
-
-
Class
-
-
-
-
B
-
-
-
Power factor
%
-
-
-
91 
91 
91 
-
-
Noise indoor
dB-A (H/M/L)
35/33/30
-
-
-
Power Level dB
57/55/52
-
-
-
Noise outdoor
dB-A  (H/L)
-
45/-
-
-
Power Level dB
-
64/-
-
-
H
E
A
T
I
N
G
Capacity
kW
4.0 
4.0 
4.0 
-
-
-
1.5 
5.0 
BTU/h
13600
13600
13600
-
-
-
5100
17100
Current
A
0.42 
0.43 
0.44 
4.20 
4.00
3.80
-
-
Input power
W
90
95
100
0.840k
0.835k
0.830k
-
-
TOTAL W
-
0.930k
0.930k
0.930k
290
1.250k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.30 
4.30/A
4.30 
5.17
4.00
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
3.6 
-
-
-
Tbivalent
°C
-
-
-
-
-10 
-
-
-
SCOP
(W/W)
-
-
-
-
3.8 
-
-
-
Annual consumption
kWh
-
-
-
-
1324 
-
-
-
elbu(-10°C)
kW
-
-
-
-
0.00
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
91 
91 
91 
-
-
Noise indoor
dB-A (H/M/L)
35/33/30
-
-
-
Power Level dB
57/55/52
-
-
-
Noise outdoor
dB-A (H/L)
-
46/-
-
-
Power Level dB
-
66/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A)  /  Max Input power(W)
0.60/130
0.62/140
0.63/150
11.0/2.20k
11.0/2.30k
11.0/2.40k
-
Starting current(A)/Comp output(W)
-
-
-
4.35/1.1k
4.15/1.1k
3.95/1.1k
-
Network Impedance(ΩMAX.)
-
-
Fan motor output (Indoor/Outdoor) W
60
60
-
Moisture removal volume
L/h(Pt/h)
2.1
 
(4.4)
-
-
External static pressure
Pa
25 (MAX80)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
14.0/12.0/10.0 (494)/(424)/(353) 
-
-
-
Heating
m³/min (ft³/min)
14.0/12.0/10.0 (494)/(424)/(353) 
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
38.0
(1342)
-
-
Heating
m³/min (ft³/min)
-
38.0
(1342)
-
-
Refrigerant type  /  amount g(oz)
-
R410A
1.40k
(49.4)
-
  Product dimension
Height mm(inch)
250 (9-27/32)
619 (24-3/8)
-
Width
mm(inch)
780 [+100] 30-45/64 [+3-15/16])
799 (31-29/64)
-
Depth
mm(inch)
650 (25-19/32)
299 (11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
-
-
-
Packing dimension
Height mm(inch)
338 (13-5/16)
688 
-
Width
mm(inch)
991 (39-1/64)
931 
-
Depth
mm(inch)
761 (29-61/64)
422 
-
Weight
(NET)
kg(lb)
29 (64)
39 (86)
-
(GROSS)  kg(lb)
34 (75)
44 (97)
-
Panel (NET)  kg(lb)
-
-
-
Layers limit  (actually)
5 (6) 
5 (6) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
Max Working Pressure HP/LP Mpa (bar)
4.15/2.70 (41.5/27.0)
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
3 ~ 40m
(9.8 ~ 131.2)
-
Indoor unit & Outdoor unit height difference  m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
20g/m 
(0.215)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1 : In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 :  If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall  
 be used.
*3 : Network Impedance shall be applicable for EUROPE and CHINA models. 
*4 : The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 : EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.