1-1.  Unit Specifications
PE1
4. Low Silhouette Ducted Type S-140PF1E5B / U-140PE1E8A
INDOOR
MODEL
S-140PF1E5B
-
-
OUTDOOR
MODEL
-
U-140PE1E8A
-
Branch pipe
MODEL
-
Performance test condition
ISO13253  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
14.0
14.0
14.0
-
-
-
3.3
15.5
BTU/h
47800
47800
47800
-
-
-
11300
52900
Current
A
1.55
1.50
1.47
6.69
6.42
6.18
-
-
Input power
W
225
225
225
4.085k
4.085k
4.085k
-
-
TOTAL W
-
4.310k
4.310k
4.310k
840
6.000k
Annual consumption
TOTAL kWh *
4
-
-
2155
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.25
3.25 / A
3.25
3.93
2.58
Erp
*
6
Pdesign
kW
-
-
-
-
14.0
-
-
-
η 
s,c
%
-
-
-
-
212.8
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
93
92
92
-
-
Noise indoor
dB-A (H/M/L)
40/36/33
-
-
-
Power Level dB
62/58/55
-
-
-
Noise outdoor
dB-A (H/L)
-
54/-
-
-
Power Level dB
-
71/-
-
-
H
E
A
T
I
N
G
Capacity
kW
16.0
16.0
16.0
-
-
-
4.1
18.0
BTU/h
54600
54600
54600
-
-
-
14000
61400
Current
A
1.55
1.50
1.46
6.64
6.35
6.15
-
-
Input power
W
225
225
225
4.215k
4.215k
4.215k
-
-
TOTAL W
-
4.440k
4.440k
4.440k
900
5.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.60
3.60 / A
3.60
4.56
3.05
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
14.0
-
-
-
Tbivalent
°C
-
-
-
-
-7
-
-
-
η 
s,h
%
-
-
-
-
142.3
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
96
96
95
-
-
Noise indoor
dB-A (H/M/L)
40/36/33
-
-
-
Power Level dB
62/58/55
-
-
-
Noise outdoor
dB-A (H/L)
-
55/-
-
-
Power Level dB
-
71/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
(Q11.5kW/W5.800kW/COP1.98)
-
Max Current(A) / Max Input power(W)
1.91/285
1.86/285
1.81/285
11.0/6.800k 11.0/7.150k 11.0/7.450k
-
Starting current(A) / Comp output(W)
-
-
-
6.69/3.0k
6.42/3.0k
6.18/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
200
90×2
-
Moisture removal volume
L/h(Pt/h)
9.0
(18.9)
-
-
External static pressure
Pa
100 (MIN10 - MAX150)
-
-
Indoor  
Air flow 
Cooling
m³/min (ft³/min)
36.0/32.0/25.0 (1271)/(1130)/(883)
-
-
-
Heating
m³/min (ft³/min)
36.0/32.0/25.0 (1271)/(1130)/(883)
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
135.0
(4767)
-
-
Heating
m³/min (ft³/min)
-
120.0
(4238)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290  (11-13/32)
1416  (55-3/4)
-
Width
mm(inch)
1400  (55-1/8)
940  (37-1/32)
-
Depth
mm(inch)
700  (27-9/16)
340  (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1614
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
45   (99)
98   (216)
-
(GROSS)  kg(lb)
54   (119)
108   (238)
-
Layers limit (actually)
9 (10) 
1 (2) 
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m 
(0.538)
-
Pipe length for additional gas  m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:  If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:  η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   27
19/09/26   17:01:41
Page of 127
Display

Click on the first or last page to see other U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B service manuals if exist.