U-4LE1E5, U-4LE1E8, U-5LE1E5, U-5LE1E8, U-6LE1E5, U-6LE1E8 - Panasonic Air Conditioner Service Manual (repair manual). Page 11

Read Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual online

Mini VRF SYSTEM
Address Settings
1
Mini VRF SYSTEM
Address Settings
3. Auto Address Setting
1-5
3-1. Auto Address Setting
Basic wiring diagram: Example (1)
• If link wiring is not used
(The inter-unit control wires are not connected to multiple refrigerant systems.)
Indoor unit addresses can be set without operating the compressors.
(S004)
ON
1
2
ON
OFF
(S003)
(S002)
1-1
1-2
1-3
1-8
(1) Automatic Address Setting from the Outdoor Unit
1
(These are the settings at the time of factory shipment.)
2
On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP switch 
(S003) is set to “0”. 
To set the number of indoor units that are connected to the outdoor unit to 8 on the outdoor unit control PCB, set the 
No. of indoor units rotary switch (S004) to “8”.
3
4
Turn ON the power to the indoor and outdoor units.
On the outdoor unit control PCB, short-circuit the automatic address pin (CN-A.ADD) for 1 second or longer, then 
release it.
(Communication for automatic address setting begins.)
* To cancel, again short-circuit the automatic address pin (CN-A.ADD) for 1 second or longer, then pull it out. 
The LED that indicates that automatic address setting is in progress turns OFF and the process is stopped.
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)
5
Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 to 3, then use the remote controller 
and complete automatic address setting. 
Refer to “Automatic Address Setting from the Remote Controller.”
No. 1 unit settings
System address 
(system 1 setting)
No. of indoor units 
(8 units setting)
Inter-unit control wiring
Unit
No. 1
Outdoor
Unit
Indoor Unit
Remote
controller
Remote control 
communication wiring
ON
ON
OFF
1
2
8
Case 1
SM830196-03_Mini_VRF SYS.indb   5
SM830196-03_Mini_VRF SYS.indb   5
2014/09/08   10:46:54
2014/09/08   10:46:54
Page of 127
Display