U-4LE1E5, U-4LE1E8, U-5LE1E5, U-5LE1E8, U-6LE1E5, U-6LE1E8, S-15M, S-22M, S-28M, S-36M, S-45M, S-60M, S-73M, S-90M, S-106M, S-140M, S-160M - Panasonic Air Conditioner Service Manual (repair manual). Page 21

Read Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 / S-15M / S-22M / S-28M / S-36M / S-45M / S-60M / S-73M / S-90M / S-106M / S-140M / S-160M Service Manual online

1 - 15
1
Mini VRF SYSTEM
Control Functions
9. Indoor Special Control
9-3. Indoor Fan Speed Control
CCU intervenes in fan control of the indoor unit according to the state at the operating mode below.
The priority order of fan control by CCU is higher than that of indoor unit’s.
9-3-1. Dry mode
Indoor unit fan operated in the dry mode is controlled from CCU as shown in the below figure.
DTi 
+1 
Fan speed is “L” when thermostat ON 
Fan speed is “LL” when thermostat OFF
Fan speed set by remote controller 
DTi = (Intake temperature of indoor unit) - (Preset temperature in remote controller)
9-3-2. Heating mode
Indoor unit fan operated in the heating mode is stopped from CCU 
at the following condition.
- Discharge air temperature of indoor unit 
 20°C+XX
- High pressure sensor temperature (HPS) in outdoor unit 
 25°C+XX
- Liquid temperature (E1) in indoor unit 
 20°C+XX
* "XX" is able to be set in EEPROM on the outdoor unit’s PCB.
EEPROM setting in main outdoor unit
CODE: 2C
Setting No
XX
-10
-9
-8
-10
-9
-8
Interval of “1”
0
(factory preset mode)
20
20
SM830195-03_Mini VRF SYS.indb   15
SM830195-03_Mini VRF SYS.indb   15
2014/09/04   18:14:07
2014/09/04   18:14:07