U-4LE1E5, U-4LE1E8, U-5LE1E5, U-5LE1E8, U-6LE1E5, U-6LE1E8, S-15M, S-22M, S-28M, S-36M, S-45M, S-60M, S-73M, S-90M, S-106M, S-140M, S-160M - Panasonic Air Conditioner Service Manual (repair manual). Page 14

Read Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 / S-15M / S-22M / S-28M / S-36M / S-45M / S-60M / S-73M / S-90M / S-106M / S-140M / S-160M Service Manual online

1 - 8
1
Mini VRF SYSTEM
Control Functions
3. Special Controls
(2) Control in the Heating Mode
(2-1) Discharge temperature: less than 30°C
(2-2) Discharge temperature: over 30°C
Control hour
Outdoor unit
Compressor
Elec. cont. valve*4
Frequency 54Hz
250pulse (Max. 3 minutes)
480pulse (Max. 17 minutes)
300pulse 
(Max. 3 minutes)
Indoor unit
Fan
Elec. cont. valve*4
Preset wind speed or fixture setting to "Stop" by indoor unit control system
480pulse
Min. 2 minutes 30 seconds to Max. 23 minutes 
(Discharge degree-of-overheating: Td*1 - HPT*2>12 K*3)
Control hour
Outdoor unit
Compressor
Elec. cont. valve*4 
Frequency 22Hz
A certain pulse calculated by the outdoor air temperature and total load of indoor unit
Indoor unit
Fan
Elec. cont. valve*4
Preset wind speed or fixture setting to "Stop" by indoor unit control system
80pulse
Min. 1 minute to Max. 6 minutes 
(Discharge degree-of-overheating: Td-HPT>12 K)
*1
*2
*3
*4
Td: Discharge temperature
HPT: High pressure saturated temperature
K: Difference in temperature (1K=1°C)
Elec. cont. valve: Electronic control valve
NOTE
SM830195-03_Mini VRF SYS.indb   8
SM830195-03_Mini VRF SYS.indb   8
2014/09/04   18:14:07
2014/09/04   18:14:07