12.6. Self-diagnosis error code table
• The display screen on the wired remote control unit and the self-diagnosis LEDs (green) on the outdoor unit printed circuit board
in the outdoor unit can be used to indicate where the location of a problem is.
Refer to the table below to remove the cause of the problem, and then re-start the air conditioner system.
• If the problem disappears and operation returns to normal, the CHECK display on the remote control unit will switch off, but the
self-diagnosis LED will remain illuminated until operation is resumed.    ... illuminated. 
Wired remote 
control unit display
Outdoor unit printed circuit board 
LED
Location or problem
Check location
Abnormal 
dispaly
Detail 
dispaly
2
3
4
5
6
7
8
F15
-01
Drain level Float switch problem Drain pump and drain pipe, indoor unit
connectors
F16
-01
Louver switch problem
Louver motor, decorative panel connection 
terminal, or indoor unit louver motor
connectors
F17
-02
D.C. Fan motor problem
Indoor unit D.C.Fan motor or connection
terminals
F20
-01
Indoor temperature sensor
problem
Indoor temperature sensor lead wire or indoor 
unit connector 
-02
Remote control thermistor
problem
Remote control thermistor
F21
-01
Pipe temp. sensor problem 
(indoor unit)
Pipe temperature sensor lead wire or indoor 
unit connector 
F26
-01
Remote control transmission 
problem
Remote control unit cable and connection
terminals
F27
-01
Indoor/outdoor unit
disconnection problem
Indoor/outdoor unit connection cable and 
connection terminals, or indoor unit power 
supplies (indoor side)
-05
Indoor/outdoor unit connection 
error problem
Indoor/outdoor unit connection wire (indoor 
side)
-01
Indoor/outdoor unit
disconnection problem
Indoor/outdoor unit connection cable and 
connection terminals, or outdoor unit power 
supplies (outdoor side)
-05
Indoor/outdoor unit connection 
error problem
Indoor/outdoor unit connection wire (outdoor 
side)
F30
-01
System problem
Total capacity for the number of indoor units is 
insufficient, or over. Check the total
capacity and the number of indoor units
-02
Open phase, or reversed phase 
of supply
Check the main power supply terminal board 
connections, or switch over any two of the 
power supply wires.
F31
-01
Suction pressure protection
Insufficient refrigerant or valve operation 
(closed)
-02
High-pressure cut-off
Check the Refrigeration system
-06
4 way valve problem
Check the 4 way valve or lead wire
-10
Refrigerant system problem
Valve operation (closed), or refrigerant
system
F32
-05
Compressor overcurrent
protection
Open phase or lock in compressor
-06
Compressor discharge temp. 
protection
Insufficient refrigerant
F40
-21
Outdoor heat exchanger outlet 
temperature sensor problem
Outdoor heat exchanger outlet temperature 
sensor (COND TEMP) lead wire, connector 
-51
Compressor discharge
temperature sensor problem
Compressor discharge temperature sensor 
(DIS T. TEMP) lead wire, connector 
F41
-02
High pressure switch open circuit 
problem
High-pressure switch lead wire, connector
-12
Low pressure sensor problem
Low pressure sensor lead wire, connector or 
valve operation (closed)