CU-4E27PBD, CU-5E34PBD - Panasonic Air Conditioner Service Manual (repair manual). Page 5

Read Panasonic CU-4E27PBD / CU-5E34PBD Service Manual online

2. Specifications 
2.1 CU-4E27PBD 
 
Item 
Unit OUTDOOR 
UNIT 
Indoor Unit Combination 
 
2.2kW + 2.2kW + 2.2kW + 7.0kW 
Power Source 
 
1 Phase, 230V, 50Hz (Power supply from outdoor unit) 
Cooling Operation 
Capacity 
kW 
8.0 (3.0 ~ 9.2) 
BTU/h 
27300 (10200 ~ 31400) 
Electrical 
Data 
Running Current 
9.4 
Power Input 
kW 
1.98 (0.53 ~ 2.87) 
EER 
W/W 
4.04 (5.66 ~ 3.21) 
Noise 
Sound Pressure Level 
dB-A (H/L) 
51 / - 
Sound Power Level 
dB (H/L) 
67 / - 
Heating Operation 
Capacity 
kW 
9.4 (4.2 ~ 10.6) 
BTU/h 
32100 (14300 ~ 36100) 
Electrical 
Data 
Running Current 
9.8 
Power Input 
kW 
2.08 (0.70 ~ 3.06) 
COP 
W/W 
4.52 (6.00 ~ 3.46) 
Noise 
Sound Pressure Level 
dB-A (H/L) 
52 / - 
Sound Power Level 
dB (H/L) 
68 / - 
Maximum Current 
19.0 
Starting Current 
9.8 
Circuit Breaker Capacity 
20 
Dimension 
Height mm 
999 
Width mm 
940 
Depth mm 
340 
Net Weight 
kg 
80 
Connection Cable 
 
3 + 1 (Earth) ø1.5 mm
2
 
Pipe Length Range (1 room) 
3 ~ 25 
Maximum Pipe Length (Total Room) 
70 
Refrigerant Pipe Diameter 
Liquid Side 
mm (inch) 
6.35 (1/4) 
Gas Side 
mm (inch) 
9.52 (3/8) (E21 & E24:12.7 (1/2)) 
Compressor 
Type 
 
Hermetic Motor / Rotary 
Motor Type 
 
Brushless (4-poles) 
Rated Output 
1.70k 
Air Circulation 
Type  
Propeller 
Fan 
Motor Type 
 
DC Motor (8-poles) 
Rated Output 
90 
Fan Speed 
High (Cooling / Heating) 
RPM 
550 / 600 
Heat Exchanger 
Type 
 
Plate fin configuration forced draft type 
Tube Material 
 
Copper 
Fin Material 
 
Aluminum (Pre Coat) 
Row / Stage 
 
2 / 46 
FPI  
19 
Air Volume 
High (Cooling / Heating) 
m
3
/min 
50.4 / 55.6 
Refrigerant Control Device 
 
 
Expansion Valve 
Refrigerant Oil 
 
 
FV50S 
Refrigerant (R410A) 
 
3.40k 
 
Page of 60