10.2. Indoor Unit
10.2.1.
How To Fix Installation Plate
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 485 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 75mm.
From installation plate left edge to unit's left side is 75 mm.
From installation plate right edge to unit's right is 85 mm.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
• Always mount the installation plate horizontally by align-
ing the marking-off line with the thread and using a level
gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the left and right side edge of the instal-
lation plate. The meeting point of the extended line is the
centre of the hole. Another method is by putting measur-
ing tape at position as shown in the diagram above. The
hole centre is obtained by measuring the distance
namely 107 mm and 58 mm for left and right edge of the
installation plate respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
10.2.2.
To Drill A Hole In The Wall And
Install A Sleeve Of Piping
1. Insert the piping sleeve to the hole.
2. Cut the sleeve until it extrudes about 15 mm from the
wall.
3. Fix the bushing to the sleeve.
4. Finish by sealing the sleeve with putty or caulking com-
pound at the final stage.
10.2.3.
Installing The Ventilation Hose
Carry out work carefully not to scratch the surface of the mobile panel.
Attached accessories
Ventilation hose connection diagram
:
:
:
For left side piping, piping connection for liquid should be
about 5 mm from this line.
For left side piping, piping connection for gas should be
about 55 mm from this line.
For left side piping, piping connection cable should be
about 750 mm from this line.
Caution
When the wall is hollow, please be sure to use the sleeve for tube
ass’y to prevent dangers caused by mice biting the connecting cable.