10 Installation Instruction
10.1. Select The Best Location
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air circula-
tion.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over the rated length, additional refrigerant
should be added as shown in the table.
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
Indoor Unit
Outdoor Unit
Piping size
Rated
Length
(m)
Max
Elevation
(m)
Max.
Piping
Length
(m)
Additional
Refrigerant
(g/m)
Model
Gas
Liquid
XE9EKE
3/8”
1/4”
7.5
5
15
20
XE12EKE
1/2”
1/4”
7.5
5
15
20
Indoor/Outdoor Unit Installation Diagram