CS-XE9CKE, CU-XE9CKE, CS-XE12CKE, CU-XE12CKE - Panasonic Air Conditioner Service Manual (repair manual). Page 31

Read Panasonic CS-XE9CKE / CU-XE9CKE / CS-XE12CKE / CU-XE12CKE Service Manual online

 4. The first 30 minutes of cooling operation, (A) will be applied.
8.2.1.4. IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
 1. When the IPM temperature rises to 110°C, compressor operation will stop immediately.
 2. Compressor operation restarts after three minutes the temperature decreases to 95°C.
B. DC Peak Current Control
 1. When electric current to IPM exceeds set value of 22.5 ± 4.0 A, the compressor will stop operate. Then, operation will restart
after three minutes.
 2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after 1 minute.
 3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute.
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
8.2.1.5. Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor top temperature. The changes of frequency are as
below figure.