QLo m
3
/min (ft
3
/min) 
Cooling: 7.1 (251) - 7.1 (251) 
Heating: 7.1 (251) - 7.1 (251)  
Lo m
3
/min (ft
3
/min) 
Cooling: 7.8 (275) - 7.8 (275) 
Heating: 8.2 (290) - 8.2 (290)  
Me m
3
/min (ft
3
/min) 
Cooling: 9.3 (328) - 9.3 (328) 
Heating: 9.3 (328) - 9.3 (328)  
Hi m
3
/min (ft
3
/min) 
Cooling: 10.8 (381) - 10.8 (381) 
Heating: 11.0 (388) - 11.0 (388) 
Indoor Airflow 
SHi m
3
/min (ft
3
/min) 
Cooling: 11.0 (388) - 11.0 (388)  
Outdoor Airflow 
Hi 
m
3
/min (ft
3
/min) 
32.5 (1150) - 33.0 (1160) 
Control Device 
 
Capillary Tube 
Refrigerant Oil 
cm
3
 FV50S 
(350) 
Refrigeration Cycle 
Refrigerant Type 
g (oz) 
R410A, 1.09k (38.5) 
Height(I/D / O/D) 
mm (inch) 
290 (11-7/16) 
542 (21-11/32) 
Width (I/D / O/D) 
mm (inch) 
870 (34-9/32) 
780 (30-23/32) 
Dimension 
Depth (I/D / O/D) 
mm (inch) 
214 (8-7/16) 
289 (11-13/32) 
Weight 
Net (I/D / O/D) 
kg (lb) 
9 (20) 
32 (71) 
Pipe Diameter (Liquid / Gas) 
mm (inch) 
6.35 (1/4) / 12.70 (1/2) 
Standard length 
m (ft) 
7.5 (24.6) 
Length range (min – max) 
m (ft) 
3 (9.8) ~ 15 (49.2) 
I/D & O/D Height different 
m (ft) 
5 (16.4) 
Additional Gas Amount 
g/m (oz/ft) 
20 (0.2) 
Piping 
Length for Additional Gas 
m (ft) 
7.5 (24.6) 
Inner Diameter 
mm  
16.7 
Drain Hose 
Length mm 
650 
Fin Material 
 
Aluminium (Pre Coat) 
Fin Type 
 
Slit Fin 
Row x Stage x FPI 
 
2 x 15 x 21 
Indoor Heat Exchanger 
Size (W x H x L) 
mm 
810 x 315 x 25.4 
Fin Material 
 
Aluminium (Blue Coat) 
Fin Type 
 
Corrugate Fin 
Row x Stage x FPI 
 
2 x 24 x 17 
Outdoor Heat 
Exchanger 
Size (W x H x L) 
mm 
36.38 x 504 x 684.0:713.0 
Material  
Polypropelene 
Air Filter 
Type  
One-touch 
Power Supply 
 
Indoor 
Power Supply Cord 
10 
Thermostat  
Protection Device 
 
2-Stage Overload Protector 
 
Dry Bulb 
Wet Bulb 
Maximum 32 
23 
Cooling 
Minimum 16 
11 
Maximum 30 
Indoor Operation 
Range 
Heating 
Minimum 16 
Maximum 43 
26 
Cooling 
Minimum 16 
11 
Maximum 24 
18 
Outdoor Operation 
Range 
Heating 
Minimum -5 
-6 
 
1. 
Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air 
temperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb) 
2. 
Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F 
Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb) 
3. 
Specifications are subjected to change without prior notice for further improvement. 
 
 
 
 
 
 
 
Page of 116
Display

Click on the first or last page to see other CS-W7NKD / CS-W9NKD / CS-W12NKD / CS-W18NKD / CS-W24NKD / CU-W7NKD / CU-W9NKD / CU-W12NKD / CU-W18NKD / CU-W24NKD service manuals if exist.