15 Technical Data
230V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
2.10
1.59
0.57
1.97
1.53
0.61
1.83
1.47
0.65
1.66
1.40
0.70
19.0°C
2.12
0.62
19.5°C
2.31
1.67
0.58
2.16
1.60
0.62
2.01
1.54
0.67
1.83
1.47
0.72
22.0°C
2.52
1.73
0.59
2.35
1.66
0.63
2.19
1.61
0.68
1.99
1.53
0.73
230V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
2.73
2.07
0.75
2.55
1.98
0.81
2.37
1.91
0.86
2.16
1.81
0.93
19.0°C
2.75
0.82
19.5°C
2.99
2.17
0.77
2.80
2.08
0.82
2.60
2.00
0.88
2.37
1.91
0.95
22.0°C
3.26
2.25
0.78
3.05
2.16
0.84
2.84
2.08
0.90
2.58
1.99
0.97
230V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
3.62
2.74
1.15
3.38
2.63
1.24
3.15
2.53
1.33
2.86
2.40
1.43
19.0°C
3.65
1.26
19.5°C
3.97
2.87
1.18
3.72
2.76
1.27
3.46
2.66
1.35
3.14
2.53
1.46
22.0°C
4.33
2.98
1.20
4.05
2.87
1.29
3.77
2.76
1.38
3.42
2.64
1.49
TC - Total Cooling (kW)
Indoor 27°C/19°C
SHC - Sensible Heat Capacity (kW)
Outdoor 35°C/24°C
IP - Input Power (kw)
84
CS-VC75KE CU-VC75KE / CS-VC95KE CU-VC95KE / CS-VC125KE CU-VC125KE
Page of 101
Display

Click on the first or last page to see other CS-VC75KE / CS-VC95KE / CS-VC125KE / CU-VC75KE / CU-VC95KE / CU-VC125KE service manuals if exist.