CS-TZ60TKEW, CS-TZ71TKEW, CU-TZ60TKE, CU-TZ71TKE - Panasonic Air Conditioner Service Manual (repair manual). Page 126

Read Panasonic CS-TZ60TKEW / CS-TZ71TKEW / CU-TZ60TKE / CU-TZ71TKE Service Manual online

126 
20.2  Heat Mode Performance Data 
Unit setting: Standard piping length, Hi Fan, Heat mode at 30°C 
Voltage: 230V 
20.2.1 CS-TZ60TKEW/CU-TZ60TKE 
Indoor (°C) 
Outdoor WB (°C) 
DB 
-15 -7  2  7  12 
TC IP TC IP TC IP TC IP TC IP 
24  4179 2052 4751 2405 5930 2401 6755 2089 6947 2080 
20  4319 1977 5240 2400 6160 2390 7200 2090 7516 2080 
16  4666 1872 5419 2395 6613 2029 7092 2079 8038 2088 
 
20.2.2 CS-TZ71TKEW/CU-TZ71TKE 
Indoor (°C) 
Outdoor WB (°C) 
DB 
-15 -7  2  7  12 
TC IP TC IP TC IP TC IP TC IP 
24  4509 2082 5558 2485 6902 2532 7665 2449 7883 2438 
20  4660 2006 6130 2480 7170 2520 8600 2450 8528 2438 
16  5035 1899 6340 2475 7697 2140 8047 2437 9121 2448 
 
TC     - Total Cooling Capacity (W) 
SHC  - Sensible Heat Capacity (W) 
IP      - Input Power (W) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127