Refrigeration cycle system
In order to diagnose malfunctions, make sure that
there are no electrical problems before inspect-
ing  the refrigeration cycle. Such problems include
insufficient insulation, problem with the power source,
malfunction of a compressor or a fan.
The normal outlet air temperature and pressure
of the refrigeration cycle depends on various condi-
tions; the standard values for them are shown in the
table on the right.
Normal Pressure and Outlet Air Temperature (Standard)
Cooling mode
Heating Mode
Outlet air
temperature
(
°
C)
12 ~ 16
36 ~ 45
Measure the electric current
during operation
Measure the gas side pressure
Measure the air temperature dif-
ference
Less than 8
°
C at cooling mode
Less than 14
°
C at heating mode
Troubleshooting Guide
 Condition: Indoor fan speed; High
Outdoor temperature 35
°
C at cooling mode and
7
°
C at heating mode
Gas pressure
MPa
(kg/cm
2
G)
0.4 ~ 0.6 (4 ~ 6)
1.5 ~ 2.1 (15 ~ 21)
Difference in the intake
and outlet
air temperatures
Above 8
°
C
(15 minutes after an
operation is started.)
at cooling mode
Above 14
°
C
(15 minutes after an
operation is started.)
at heating mode
Normal
Value of electric
current during operation
Higher than specified
Dusty condenser
preventing heat radiation
Excessive amount
of refrigerant
Lower than specified
Gas side
pressure
Cooling Mode
Low
Inefficient compressor
Insufficient refrigerant
Clogged strainer or
capillary tube
Inefficient compressor
Insufficient refrigerant
Clogged strainer or
capillary tube
Low
Low
Low
Low
High
Heating Mode