Deice Operation Time Chart
  • 
Compressor frequency is set at 40Hz (CU-G95KE) or 49Hz (CU-G125KE) when the deice operation starting signal is generated.
  • 
30 seconds later deice operation starting signal is generated, indoor fan, outdoor fan, 4-way valve are turned off and
compressor operates at 40Hz (CU-G95KE) or 49Hz (CU-G125KE) for 30 seconds. (Deice operation starts)
  • 
During deice operation, the compressor operating frequency is set at 58Hz (CU-G95KE) or 83Hz (CU-G125KE).
  • 
Deice will end when the outdoor heat exchanger temperature rises to 16°C or after 11 minutes.
28