2.
Cooling Operation
A. Room Temperature Control
(i) When the remote control setting temperature is less than 24°C
(ii) When the remote control setting temperature is 24°C and above
•
Compressor OFF temperature = Compressor ON temperature.
•
The operation frequency can be changed every 30 seconds.
•
30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
•
The compressor stops when the intake air temperature reaches 1°C below internal setting temperature and continues for 3
minutes.
minutes.
•
When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
•
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.
•
When the compressor stops, the outdoor fan motor stops 30 seconds later.
19
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE