2.
Cooling Operation
A. Room Temperature Control
(i) When the remote control setting temperature is less than 24°C
(ii) When the remote control setting temperature is 24°C and above
  • 
Compressor OFF temperature = Compressor ON temperature.
  • 
The operation frequency can be changed every 30 seconds.
  • 
30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
  • 
The compressor stops when the intake air temperature reaches 1°C below internal setting temperature and continues for 3
minutes.
  • 
When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
  • 
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.
  • 
When the compressor stops, the outdoor fan motor stops 30 seconds later.
19
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE