TIMER TABLE <INDOOR>
Test mode
Name
Time
(When test point
Short-circuited)
4 Way Valve abnormality
4 min.
2.4 sec.
Outdoor air temp. for Hz No. decision
30 min.
0 sec.
Anti-dew formation control
20 min.
0 sec.
Anti-freezing control
6 min.
0 sec.
Themo OFF delay
3 min.
0 sec.
Low pressure control (gas leakage) compressor OFF time
3 min.
0 sec.
Time delay safety control
2 min. 58 sec.
0 sec.
Outdoor timer status shift time
30 sec.
0 sec.
60 sec.
Intake air temp. sampling time
20 sec.
0 sec.
Auto mode judgement sampling time
1 hr.
6 sec.
24 hours ON / OFF timer
1 hour
1 min.
Heating SSHi fan speed shift
120 min.
12 sec.
Cooling SHi fan speed shift
30 min.
3 sec.
Hot start forced completion
4 min.
0 sec.
30 min.
3 sec.
Outdoor timer status shift time
90 min.
9 sec.
180 min.
18 sec.
4200 min.
42 sec.
Auto mode judgement interval
30 min.
3 sec.
Sleep mode timer shift
1 hour
6 sec.
After Hot start / Deice
2 min.
12 sec.
110
S-G95KE CU-G95KE / CS-G125KE CU-G125KE