1.4. Operation range
1.4.1. Power Supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be
balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of
the rated voltage.
MODEL
Unit Main Power
Applicable Voltage
CU-
Phase, Volts
Hz
Max
Min
L24DBE5
L28DBE5
L34DBE5
L43DBE5
1~240
50
264
216
1~220
50
242
198
1~230
50
253
207
L50DBE8
3N~380
50
418
342
3N~400
50
440
360
3N~415
50
457
374
1.4.2. Indoor and Outdoor Temperature
 • Model 50Hz CU-L24DBE5, CU-L28DBE5, CU-L34DBE5, CU-L43DBE5, CU-L50DBE8
Operating
Hz
Indoor Temp. (D.B./W.B.) (°C)
Outdoor Temp. (D.B./W.B.) (°C)
Max
Min
Max
Min
Cooling
50
32/23
21/15
43/-
-15/-
Heating
50
27/-
16/-
24/18
-20/-
4
Page of 127