CS-F24DD2E5, CS-F28DD2E5, CS-F34DD2E5, CS-F43DD2E5, CS-F50DD2E5, CU-L24DBE5, CU-L28DBE5, CU-L34DBE5, CU-L43DBE5, CU-L50DBE8 - Panasonic Air Conditioner Service Manual (repair manual). Page 10

Read Panasonic CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 Service Manual online

3.5. CS-F50DD2E5 CU-L50DBE8
ITEM / MODEL
Indoor Unit
Outdoor Unit
Main Body
CS-F50DD2E5
CU-L50DBE8
Cooling Capacity
kW
14.0
BTU/h
47,700
Heating Capacity
kW
16.0
BTU/h
54,600
Refrigerant Charge-less
m
30
Standard Air Volume for High Speed
m
3
/min
Hi 45
Hi 98
cfm
Hi 1590
3460
External Static Pressure
Pa
Hi 98
-
mmAq
Hi 10.0
Outside Dimension (H x W x D)
mm
360 x 1000 x 650
1340 x 900 x 320
inch
14-3/16 x 39-3/8 x 25-19/32
52-7/8 x 35-7/16 x 12-19/32
Net Weight
kg (lbs)
48 (106)
105 (231)
Piping
Connection
Refrigerant
Gas
mm (inch)
O.D Ø 15.88 (5/8) Flared Type
Liquid
mm (inch)
O.D Ø 9.53 (3/8) Flared Type
Drain
mm
O.D Ø 32
I.D Ø 20 x 1
Compressor
Type, Number of Set
-
Hermetic - 2P (Rotary), 1
Starting Method
-
DC - INV control
Motor
Type
-
4-pole single phase brushless motor
Rated Output
kW
-
3.8
Fan
Type, Number of Set
Sirocco Fan, 2
Mix flow fan - 2
Motor
Type
4-pole single phase induction motor
6-pole single phase induction motor
Rated Output
kW
0.27
0.07 x 2
Air-heat Exchanger (Row x Stage x FPI)
Louvre-fin type (3 x 18 x 13)
Corrugate-fin type (2 x 51 x 18)
Refrigerant Control
-
Exp. Valve
Refrigerant Oil (Charged)
cm
3
-
FV50S (1200)
Refrigerant (Charged) R410A
kg (oz)
-
3.50 (123)
Running
Adjustment
Control Switch
Wired Remote Control
-
Room Temperature
Thermostat
-
Safety Devices
Temperature, current and pressure protection control for compressor,
Internal thermostat for FM, High pressure switch,
Current trans, Crankcase heater
Noise Level
dB (A)
Cooling : Hi 49 Lo 45
Cooling 54, Heating 56
Heating : Hi 47 Lo 44
Power level dB
Cooling : Hi 64 Lo 60
Heating : Hi 62 Lo 59
Cooling 68, Heating 70
Moisture Removal
L/h
9.0
EER
W/W
2.77
COP
W/W
3.30
 1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air
temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
 2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°F
D.B.), 6°C W.B. (42.8°F W.B.)
ELECTRICAL DATA (50 Hz)
ITEM / MODEL
Condition by JIS-B8615
Volts
V
380
400
415
Phase
3N
3N
3N
Power Consumption
kW
Cool
5.06
5.06
5.06
Heat
4.85
4.85
4.85
Running Current
A
Cool
8.0
7.7
7.4
Heat
7.7
7.4
7.2
Starting Current
A
8.0
7.7
7.4
Power Factor
%
Cool
96
95
95
Heat
96
95
94
*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Panasonic
Power source
AC, 3N~380V, 400V, 415V 50Hz
10
Page of 127
Display

Click on the first or last page to see other CS-F24DD2E5 / CS-F28DD2E5 / CS-F34DD2E5 / CS-F43DD2E5 / CS-F50DD2E5 / CU-L24DBE5 / CU-L28DBE5 / CU-L34DBE5 / CU-L43DBE5 / CU-L50DBE8 service manuals if exist.