HC: Heating Capacity
IPT: Heating Power Consumption
Model
Heating capacities are based on conditions
CS-F28DB4E5
Single phase, 50Hz 230V, Three phase, 50Hz 400V
Heating capacity
Indoor temp. 20
°C D.B.
8kW
Outdoor temp. 7
°C D.B. 6°C W.B.
Standard air volume 20 m
3
/min
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
-6
°C
0
°C
6
°C
12
°C
Air
HC
HC
HC
HC
D.B.
kW
kW
kW
kW
15
5.84
7.00
8.40
9.76
20
5.52
6.60
8.00
9.60
25
5.20
6.24
7.60
9.20
Ambient
Temperature Air Entering Condenser (
°C D.B.)
Return
-6
°C
0
°C
6
°C
12
°C
Air
IPT
IPT
IPT
IPT
D.B.
kW
kW
kW
kW
15
1.82
2.08
2.47
2.91
20
1.92
2.21
2.60
3.02
25
2.03
2.34
2.73
3.05